Mitsubishi Electric s-MEXT-G00 006 Technical Manual page 60

Computer room air conditioner
Table of Contents

Advertisement

TM_s-MEXT_ME28relC_00_12_19_EN
N. Par.
Description
24.24
Humidity differential for the update of the reading of probe T+H 128
24.25
Temperature differential for the update of the reading of probe T+H 129
24.26
Humidity differential for the update of the reading of probe T+H 129
26.01
Number of units in LAN
26.02
Configuration of average calculation function in LAN [0: Disabled | 1: Enabled]
26.03
Configuration of standby mode function in LAN [0: Disabled | 1: Enabled]
26.04
Standby cycle time in LAN
26.05
Configuration of number of units on standby in LAN [0: 1 unit | 1: 2 units]
26.06
Configuration of standby mode limits function in LAN [0: Disabled | 1: Enabled]
26.11
Enable the H&L Local Temperature Protection function [0: Disabled | 1: Enabled]
26.12
Hot Spot function On differential
26.13
Cold Spot function On differential
26.14
Time before protection Off when the temperature is between the limits of the Cold and Hot Spot
26.15
Time before protection On when outside the limit of the Hot or Cold Spot
26.16
Enable the Active Fan on Standby function [0: Disabled | 1: Enabled]
26.17
Internal fan speed with Active Fan on Standby in use
26.18
Enable the Active Pressure Load function [0: Disabled | 1: Enabled]
26.19
APL operation enable in case of pressure transducer alarm [0: Disabled | 1: Enabled]
26.20
Enable the H&L Local Pressure Protection function [0: Disabled | 1: Enabled]
26.21
High local pressure function On differential
26.22
Low local pressure function On differential
26.23
Time before protection Off when the temperature is between the high and low local pressure limits
26.24
Time before protection On when outside the limit of the high or low local pressures
27.02
Heating element configuration [0: Disabled | 1: Enabled]
27.03
Heating element type [0: ON/OFF | 1: Modulanting]
27.04
Humidity probe configuration [0: Disabled | 1: Enabled]
27.05
Humidifier configuration [0: Disabled | 1: Internal]
27.06
Humidifier model configuration (cylinder type)
27.07
Maximum steam production
27.16
Enable the humidifier periodical drain function [0: Disabled | 1: Enabled]
27.17
Delay before each periodical drain
27.18
Enable the humidifier inactive draining function [0: Disabled | 1: Enabled]
27.19
Delay before each draining during inactivity
27.09
Dehumidifier configuration [0: Disabled | 1: Enabled]
27.11
Delivery air damper configuration [0: Disabled | 1: Enabled]
27.12
Damper opening stroke time
27.13
Presence of network transducer
Type of power supply system [0: 3-ph unbalanced 3/4-wires | 1: 1-ph 2-wires | 2: 2-ph 3-wires | 3: 3-ph
27.14
balanced 3-wires | 4: 3-ph balanced load | 5: 3-ph Aron system]
27.15
Input current transformation ratio
27.20
Setpoint offset function enable [0: Disabled | 1: Enabled]
Setpoint offset signal type [0: 0-1V
27.21
External T+H]
Technical manual
| 1: 0-5 V
| 2: 0.5-4.5V
| 3: 0-20mA | 4: 4-20mA | 5: Remote T+H | 6:
DC
DC
DC
TRANSLATION OF THE ORIGINAL INSTRUCTIONS
60
Default
U.M.
Min.
0.5
%UR
0.1
0.5
°C
0.1
0.5
%UR
0.1
1
-
1
0
-
0
0
-
0
168
-
0
0
-
0
1
-
0
0
-
0
2.0
°C
0.5
2.0
°C
0.5
300
s
10
60
s
10
0
-
0
70
%
P 99.01
0
-
0
0
-
0
0
-
0
10
Pa
2
10
Pa
2
300
s
10
60
s
10
0
-
0
0
-
0
0
-
0
0
-
0
0
-
0
100
%
10
0
-
0
24
h
0
0
-
0
3
d
1
0
-
0
0
-
0
120
s
0
0
-
0
5
-
0
20
-
1
0
-
0
0
-
0
Max.
2.0
2.0
2.0
16
1
1
999
1
1
1
99.9
99.9
600
600
1
100
1
1
1
999
999
600
600
1
1
1
1
121
100
1
240
1
99
1
1
500
1
5
32767
1
6