Configuration Tab - Rockwell Automation Allen-Bradley 35E User Manual

Ac drives
Table of Contents

Advertisement

Chapter 8
Develop Secure Applications
192
Disable the Ethernet Port on the FactoryTalk Linx Port Configuration
Tab
You can disable the Ethernet ports on the Armor PowerFlex drive using
FactoryTalk Linx.
IMPORTANT Once a port is disabled, it cannot be used with FactoryTalk Linx.
So if both ports are disabled, FactoryTalk Linx will not be able to
communicate with the unit.
The Armor PowerFlex will have to be reset to factory default to
enable communication again, see
page
Perform the following steps to disable a port of the Armor PowerFlex drive,
using FactoryTalk Linx.
1. Launch the FactoryTalk Linx and create the appropriate EtherNet driver
if needed.
2. Once you see the Armor PowerFlex IP Address listed under the EtherNet
Driver, go to the advance settings as shown.
Rockwell Automation Publication 35-UM001A-EN-P - May 2022
Reset to Out-of-Box State on
89.

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Allen-Bradley 35E and is the answer not in the manual?

Subscribe to Our Youtube Channel

This manual is also suitable for:

Allen-bradley 35s

Table of Contents

Save PDF