Chapter 8
Develop Secure Applications
192
Disable the Ethernet Port on the FactoryTalk Linx Port Configuration
Tab
You can disable the Ethernet ports on the Armor PowerFlex drive using
FactoryTalk Linx.
IMPORTANT Once a port is disabled, it cannot be used with FactoryTalk Linx.
So if both ports are disabled, FactoryTalk Linx will not be able to
communicate with the unit.
The Armor PowerFlex will have to be reset to factory default to
enable communication again, see
page
Perform the following steps to disable a port of the Armor PowerFlex drive,
using FactoryTalk Linx.
1. Launch the FactoryTalk Linx and create the appropriate EtherNet driver
if needed.
2. Once you see the Armor PowerFlex IP Address listed under the EtherNet
Driver, go to the advance settings as shown.
Rockwell Automation Publication 35-UM001A-EN-P - May 2022
Reset to Out-of-Box State on
89.