Sharp JW-20CM User Manual page 75

Programmable controller
Table of Contents

Advertisement

From the previous page
Writing to the EEPROM of the JW-20CM, start operation
· Write "81
" into parameter address 003777
(H)
EEPROM of the JW-20CM. Then start the remote I/O operate.
· After starting operation, the setting value changes to "01
Setting
value
(H)
Stop operation of the remote I/O (initial value)
0 0
(H)
· Calculate BCC of parameter addresses 000000 to 003775
When normal, the remote I/O will start operation.
0 1
When abnormal, the module will output error code BE
① Check the parameter contents
When normal, the module calculates BCC and writes the check sum
value into address 003776
When abnormal, it outputs a BF
② Changes the value to 00
8 0
(H)
writes it into the EEPROM.
If a write error to the EEPROM occurs, it outputs a 30
keeps the value set to 80
Writing to the EEPROM of the JW-20CM, start operation
① Check the parameter contents
When normal, the module calculates BCC and writes the check sum
value into address 003776
When abnormal, it outputs a BF
② Changes the value to 01
8 1
(H)
writes it into the EEPROM.
If a write error to the EEPROM occurs, it outputs a 30
keeps the value set to 81
Writing to the EEPROM of the JW-20CM, start operation
0 8
Initialize setting values of parameter addresses 000000 to 003777
(Operation example of JW-13PG)
Display the contents of address
003777
(8)
PC operation
Turning a master station PC to monitor or change mode (PC operation).
(Operation example of JW-13PG)
and write the set parameter contents into the
(8)
Contents
.
(8)
error code.
(H)
(stops the operation of the remote I/O), and
(H)
.
(H)
.
(8)
error code.
(H)
(starts the operation of the remote I/O), and
(H)
.
(H)
Write 81
(H)
Monitor mode
Change mode
8
37
·
[HEX (hexadecimal), byte]
."
(H)
.
(8)
.
(H)
error code and
(H)
error code and
(H)
(8)
Screen display of JW-13PG
03775
HEX
03776
HEX
I PARAM.
>03777
HEX
8
00
00
01