7-8 Wiring to power supply module
[1] JW-1PU
· Open the terminal block cover, fasten with the screw with torque of less than 12kg·cm.
· A maximum of three halt output lines can be connected serial. To use more than three sets, use
a relay for interconnection.
In case of 100 VAC input
7
In case of using DC output module, connect the AC relay in the halt output line and insert the
contact with the emergency stop circuit.
In case of 200 VAC input
· In case of using 200 VAC, switched to the 200 V side in terminal block of power supply module.
· If 200 V is added with the clip connected to the 100 V side, it may damage the power supply
module.
100 VAC
or 200 VAC
GND
DC relay
The coil rating must conform to the power supply voltage.
In case of 100 VAC input
SHORT
200 VAC
SHORT
100 VAC
200 VAC
input
GND
In case of 100 VAC input Terminal block cover
1
SHORT
200 VAC
2
SHORT
100 VAC
3
INPUT
4
5
Terminal block
cover
6
7
halt output
line
8
1
2
7
1A
3
4
8
5
6
Halt output internal circuit
7
8
·
SSR