Hydac CSI-C-11 Operating	 Instruction
Hide thumbs Also See for CSI-C-11:
Table of Contents

Advertisement

Quick Links

CSI-C-11
ConditionSensor Interface
Operating Instruction
English (translation of original instructions)
Document No. : 4548075a
Follow these instructions for proper and safe use.
Keep for future reference.

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the CSI-C-11 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Hydac CSI-C-11

  • Page 1 CSI-C-11 ConditionSensor Interface Operating Instruction English (translation of original instructions) Document No. : 4548075a Follow these instructions for proper and safe use. Keep for future reference.
  • Page 2 Executive directors: Mathias Dieter, Dipl.Kfm. Wolfgang Haering Documentation Representative The contact data of the Documentation Representative is: Günter Harge c/o HYDAC International GmbH, Industriegebiet, 66280 Sulzbach / Saar Germany Telephone: +49 6897 509 1511 Fax: +49 6897 509 1394 E-mail: guenter.harge@hydac.com Print date: 6/3/2022 ©...
  • Page 3: Table Of Contents

    Assembling the CSI .................. 27 Connection overview .................. 29 5.2.1 Pin assignment – DC IN / HSI............ 30 5.2.2 Pin assignment – Sensor 1 IN............ 30 5.2.3 Pin assignment – Sensor 2 IN............ 31 5.2.4 Pin assignment - LAN connection............ 31 BeWa CSI-C-11 4548075 from_V250-V253 en-us web...
  • Page 4 Opening/displaying/operating the web interface via LAN .... 59 Sending measured data to the CMX ............ 60 Changing the access data for the web interface and FTP ...... 62 Performing Maintenance .................. 63 Troubleshooting/fault rectification ................ 64 10 Disposal/Recycling .................... 68 BeWa CSI-C-11 4548075 from_V250-V253 en-us web...
  • Page 5 HYDAC FILTER SYSTEMS GMBH Table of Contents Appendix ........................  69 Contacting Customer Service............... 69 Finding accessories.................. 70 A.2.1 ZBECSI 60 connection adapter - Connection overview.... 74 Glossary .........................  78 Index ........................ 81 BeWa CSI-C-11 4548075 from_V250-V253 en-us web...
  • Page 6: General

    Additionally, please observe the product- related instructions and requirements. Operator, specialist Read, observe and follow this manual and personnel: the associated documents, in particular, the safety and warning instructions. Tab. 1: Target group 6 / 84 BeWa CSI-C-11 4548075 from_V250-V253 en-us web...
  • Page 7: Illustrations In The Manual

    Supplementary instructions regarding the validity of the manual (optional) Please note that you can directly access information through the directories. However, this does not release you from the obligation to read this manual fully before commissioning. BeWa CSI-C-11 4548075 from_V250-V253 en-us web 7 / 84...
  • Page 8: Representation Of Requirements

    Procedural instructions with a random sequence Procedural instructions that have a random sequence are listed as bullet points (-). An example of a procedural instruction with a random sequence: – Clean the display. 8 / 84 BeWa CSI-C-11 4548075 from_V250-V253 en-us web...
  • Page 9: Representation Of Intermediate Results/Results

    An example for a procedural instruction with intermediate result and final result: 1. Switch the product on. ð The display lights up. 2. Press the button. O The product is now ready for use. BeWa CSI-C-11 4548075 from_V250-V253 en-us web 9 / 84...
  • Page 10: Supplementary Symbols

    Warning/General Safety Information, which is placed ahead of each activity, are represented as follows: CAUTION Type and source of danger Consequence of the danger Hazard symbol Measures to avert danger ► 10 / 84 BeWa CSI-C-11 4548075 from_V250-V253 en-us web...
  • Page 11: Signal Words And Their Meaning In The General Safety Information

    ENVIRONMENTALLY TIP ENVIRONMENTALLY TIP – The signal word indicates a hazardous situation without a high level of risk, which, if not avoided, will result in environmental contamination. BeWa CSI-C-11 4548075 from_V250-V253 en-us web 11 / 84...
  • Page 12: Exclusion Of Liability / Warranty

    Any infringements to the above shall be liable to damage compen- sation. 12 / 84 BeWa CSI-C-11 4548075 from_V250-V253 en-us web...
  • Page 13: Safety Information

    The following risks could arise during the commissioning / operation life phase: NOTICE Identical bus addresses of HSI SMART sensors Faulty or no communication. u Note the different bus addresses of the HSI SMART sensors. BeWa CSI-C-11 4548075 from_V250-V253 en-us web 13 / 84...
  • Page 14 2 | Safety information HYDAC FILTER SYSTEMS GMBH NOTICE Incorrect sensor Faulty or no communication. u Connect the CSI-C-11 only to the HSI SMART sensors or the permitted analog sensors. NOTICE Connection of more than two HSI SMART sensors Faulty or no communication.
  • Page 15: Product And Technical Specifications

    Limit values are set depending on the measured variable with the aid of a wizard and, if the limit values are exceeded, the CSI-C-11 will auto- matically send out an alarm by e-mail or via the integrated Ethernet and fieldbus interface (Modbus®).
  • Page 16: Scope Of Delivery

    Before commissioning the unit, check the contents of the package for completeness. The following items are supplied: Qty. Description ConditionSensor Interface CSI-C-11 Operating instructions (this document) Tab. 2: Scope of Delivery 16 / 84 BeWa CSI-C-11 4548075 from_V250-V253 en-us web...
  • Page 17: Dimensions

    HYDAC FILTER SYSTEMS GMBH Product and technical specifications | 3 3.2 Dimensions The CSI-C-11 has the following dimensions. Fig. 2: CSI-C-11 dimensions All dimensions in mm. BeWa CSI-C-11 4548075 from_V250-V253 en-us web 17 / 84...
  • Page 18: Proper/Designated Use

    3 | Product and technical specifications HYDAC FILTER SYSTEMS GMBH 3.3 Proper/Designated Use Use the ConditionSensor Interface CSI-C-11 only for the appli- cation described below. Depending on the device type, the ConditionSensor Interface CSI-C-11 serves to implement digital (HSI SMART sensors with Hydac Sensor Interface HSI) and analog sensors signals (e. g.
  • Page 19: Improper Use Or Use Deviating From Intended Use

    – Operating with sensors that are not permitted. – Operating with more than two HSI SMART sensors. – Operating with more than four permitted analog sensors. – Modifications to the interface made by the user or purchaser. BeWa CSI-C-11 4548075 from_V250-V253 en-us web 19 / 84...
  • Page 20: Technical Data

    3 | Product and technical specifications HYDAC FILTER SYSTEMS GMBH 3.5 Technical Data The technical data of the CSI-C-11 is as follows: HSI interface HYDAC Sensor Interface to connect two HSI SMART sensors Analog interface Sensor interface to connect maximum four analog sensors (type can be selected): - 4 … 20 mA (load: 500 Ω)
  • Page 21: Tab. 5 Electrical Data

    Permissable relative humidity 0 - 70%, non-condensing Permitted storage temperature -30 … 85 °C range Protection class according to IP66 40050 Housing dimensions 131 x 77.5 x 35.5 mm Body Aluminum housing Weight ≈ 360 g Tab. 7: Other data BeWa CSI-C-11 4548075 from_V250-V253 en-us web 21 / 84...
  • Page 22: Decoding The Model Code Label

    3.6 Decoding the model code label Details for identifying the product are found on the name plates on the product as well as their components. Always mention the part no. and the serial no. when contacting HYDAC. Fig. 3: Name plate Description Model For details, see Model code [} 23]...
  • Page 23: Model Code

    HYDAC FILTER SYSTEMS GMBH Product and technical specifications | 3 3.6.1 Model code The model code of the CSI-C-11 is the following: CSI - C - 11 - 0 - 0 - 0 /- 000 Product series CSI = ConditionSensor Interface...
  • Page 24: Sensor Overview And Functions

    HYDAC Fluid Monitoring Module FMM, the HYDAC ContaminationSensor Module CSM or the HYDAC ConditionMonitoring Package CMP. By connecting up to two HSI SMART and four analog sensors, the CSI-C-11 functions as a compact Fluid Condition Monitoring solution in combination with the mentioned modules and is an essential component for implementing modern maintenance strategies such as Predictive and Proactive Maintenance.
  • Page 25: Fig. 5 Connection Overview

    Product and technical specifications | 3 Fig. 5: Connection overview LAN Lokal Aera Network W-LAN Wireless Lokal Aera Network Sensor 2 IN Sensor 2 input Sensor 1 IN Sensor 1 input DC IN / HSI Power supply LED Status LED, for details see Operation [} 45]. BeWa CSI-C-11 4548075 from_V250-V253 en-us web 25 / 84...
  • Page 26: Storage And Transport

    Store the CSI in a clean, dry place, in the supplied packaging as far as is possible. Only remove the packing just before installing the unit. Observe the storage conditions given in Chapter Technical Data [} 20]. 26 / 84 BeWa CSI-C-11 4548075 from_V250-V253 en-us web...
  • Page 27: Assembly, Installation And Commissioning

    This chapter provides information on assembly, installation and commissioning. 5.1 Assembling the CSI The CSI-C-11 has an assembly plate with two boreholes for wall mounting or mounting on an electric motor. The position of the CSI can be as required while doing this.
  • Page 28: Fig. 7 Example: Csi-C-11 Assembled On A Csm-E

    5 | Assembly, installation and commissioning HYDAC FILTER SYSTEMS GMBH Fig. 7: Example: CSI-C-11 assembled on a CSM-E Fig. 8: Example: CSI-C-11 assembled on a motor-pump assembly 28 / 84 BeWa CSI-C-11 4548075 from_V250-V253 en-us web...
  • Page 29: Connection Overview

    HYDAC FILTER SYSTEMS GMBH Assembly, installation and commissioning | 5 5.2 Connection overview Connect the CSI-C-11 to the sensors and the supply voltage as shown below. Fig. 9: Connection overview LAN Lokal Aera Network W-LAN Wireless Lokal Aera Network Sensor 2 IN Sensor 2 input Sensor 1 IN Sensor 1 input DC IN / HSI Power supply...
  • Page 30: Pin Assignment - Dc In / Hsi

    HSI SMART HSI Signal input Sensor 1 Analog sensor 3 Analog input 3 Analog sensor 4 Analog input 4 A1 – A4 GND Analog sensor Analog input GND 1 - 4 Tab. 10: Pin assignment – Sensor 1 IN 30 / 84 BeWa CSI-C-11 4548075 from_V250-V253 en-us web...
  • Page 31: Pin Assignment - Sensor 2 In

    Ethernet port for data reception + ETH TX- Network (LAN) Ethernet port for data transmission - Fig. 13: LAN ETH RX- Network (LAN) Ethernet port for data reception - Tab. 12: Pin assignment - LAN connection BeWa CSI-C-11 4548075 from_V250-V253 en-us web 31 / 84...
  • Page 32: Csi-C-11 - Connection Examples

    5 | Assembly, installation and commissioning HYDAC FILTER SYSTEMS GMBH 5.2.5 CSI-C-11 - Connection examples Here, you will find connection examples for the CSI-C-11. Fig. 14: Connection example CSI-C-11-0-0-0 32 / 84 BeWa CSI-C-11 4548075 from_V250-V253 en-us web...
  • Page 33: Fig. 15 Connection Example Csi-C-11 - Cs1000 - Hda48X6-A - Ets7246-B

    HYDAC FILTER SYSTEMS GMBH Assembly, installation and commissioning | 5 Fig. 15: Connection example CSI-C-11 - CS1000 - HDA48x6-A - ETS7246-B BeWa CSI-C-11 4548075 from_V250-V253 en-us web 33 / 84...
  • Page 34: Fig. 16: Connection Example Zbe Csi 60

    5 | Assembly, installation and commissioning HYDAC FILTER SYSTEMS GMBH Fig. 16: Connection example ZBE CSI 60 For further details on the ZBE CSI 60 connections, see ZBECSI 60 connection adapter - Connection overview [} 74]. 34 / 84 BeWa CSI-C-11 4548075 from_V250-V253 en-us web...
  • Page 35: Commissioning

    5.3.1.2 Setting the CSI via LAN To set the CSI via the LAN connection, proceed as follows: ü The CSI-C-11 is connected to the end device with a LAN cable. 1. Enter the IP address of the CSI in the browser of your end device.
  • Page 36: Setting The Csi Via W-Lan

    The CSI-C-11 logs in with the SSID: HYDAC_AP. (Default settings) 2. Enter the IP address 192.168.0.30 in the browser of your end device. O You will reach the web interface of the CSI-C-11. Use a suitable JavaScript-enabled browser such as Google Chrome, Mozilla Firefox, Apple Safari or Microsoft Edge.
  • Page 37: Factory Settings

    Date for the data logger. Analog 1 … 4 Parameterizing the connected analog sensors. (Only in CSI-C-11-x- x-1) Channel Type Analog channel type can be selected between: -OFF - 4 … 20 mA, - 0 … 20 mA, - 0 … 10 V BeWa CSI-C-11 4548075 from_V250-V253 en-us web 37 / 84...
  • Page 38 Downtime costs Risk Risk of failure Hydraulic Component Selection of the component according (select most to the Contamination Handbook sensitive) Pressure Level Selection of the pressure range according to the Contamination Handbook 38 / 84 BeWa CSI-C-11 4548075 from_V250-V253 en-us web...
  • Page 39 ID of the CMX station for which the data should be written Datapoint ID First data point ID of the CMX data points that are transferred Save Time Storage interval in which the data is written in CMX BeWa CSI-C-11 4548075 from_V250-V253 en-us web 39 / 84...
  • Page 40: Tab. 14 Description Of The Default Settings

    New password that should be assigned Repeat new Repeat input of the assigned password password Use authentication? Activation of the authentication for the web interface login Tab. 14: Description of the default settings 40 / 84 BeWa CSI-C-11 4548075 from_V250-V253 en-us web...
  • Page 41: Overview Of The Default Settings

    Analog 2 Channel Type OFF Name Analog 2 Unit Lower Range 0 Analog 3 Channel Type OFF Name Analog 3 Unit Lower Range 0 Analog 4 Channel Type OFF Name Analog 4 BeWa CSI-C-11 4548075 from_V250-V253 en-us web 41 / 84...
  • Page 42 Light Contaminatio Minimal n Sensitivity System Life 0…1000 h Expectancy Cost of Component Replacement Cost of Downtime Risk Contamination Hydraulic Costum Handbook Component Pressure < 140 bar Level Alerting active? false 42 / 84 BeWa CSI-C-11 4548075 from_V250-V253 en-us web...
  • Page 43 Server Address server.adress.com Server Port Server User cmxUserName Name Server User cmxUserPassord Password Station ID 123456789 Datapoint ID 123456789 Save Time Webinterface Username Hydac Settings Current Password New Password Repeat New Password BeWa CSI-C-11 4548075 from_V250-V253 en-us web 43 / 84...
  • Page 44 6 | Factory settings HYDAC FILTER SYSTEMS GMBH Main Menu Default settings false authentification Tab. 15: Default settings CSI-C-11-0-0-1/-000 44 / 84 BeWa CSI-C-11 4548075 from_V250-V253 en-us web...
  • Page 45: Operation

    Note the status LED on the CSI during operation. Status LED Fig. 17: Status LED Status LED Description color LED does not No power supply light up Orange Boot phase Green Operation Red Errors, see chapter Troubleshooting/fault rectification [} 64] BeWa CSI-C-11 4548075 from_V250-V253 en-us web 45 / 84...
  • Page 46: Evaluating/Reading Measurement Protocols/Values

    – Data is transmitted only by means of a wireless connection between the mobile device and the sensor / interface such as the W-LAN or Bluetooth (depending on the device) – Free download) 46 / 84 BeWa CSI-C-11 4548075 from_V250-V253 en-us web...
  • Page 47 HYDAC sensors into your own user environment / software. To this end, you will have access to all the HYDAC program libraries, a detailed description and help, as well as example programs in various programming languages.
  • Page 48: Reading The Measured Values Via Modbus

    (High Byte first). You can set two different formats for the registers, New Format or Old Format . For more details, see Input Register mapping - New format [} 49] or Input Register mapping - Old format [} 51]. 48 / 84 BeWa CSI-C-11 4548075 from_V250-V253 en-us web...
  • Page 49: Input Register Mapping - New Format

    Channel 8 (32bit) 0x0018 + Register Offset high byte 0x0019 + Register Offset low byte Channel 9 (32bit) 0x001A + Register Offset high byte 0x001B + Register Offset low byte BeWa CSI-C-11 4548075 from_V250-V253 en-us web 49 / 84...
  • Page 50: Tab. 16 Input Register Mapping - New Format

    0x0038 + Register Offset high byte 0x0039 + Register Offset low byte Tab. 16: Input Register Mapping - New Format The Offset register can be parameterized in the dialog menu (default settings: 0x0000). 50 / 84 BeWa CSI-C-11 4548075 from_V250-V253 en-us web...
  • Page 51: Input Register Mapping - Old Format

    … … … Sensor 2 + analog Input Register (Offset module 0x8000) Device ID (16 char- 0x8000 acters) 0x8001 8 registers with 2 0x8002 characters each 0x8003 0x8004 0x8005 0x8006 0x8007 BeWa CSI-C-11 4548075 from_V250-V253 en-us web 51 / 84...
  • Page 52: Tab. 17 Input Register Mapping - Old Format

    0xA03F low byte Tab. 17: Input register mapping - Old format You can view the assignment of the input registers via the sensor dialog. The assignment depends on the connected sensors. 52 / 84 BeWa CSI-C-11 4548075 from_V250-V253 en-us web...
  • Page 53: As1000

    The assignment depends on the connected sensors. Fig. 18: Input Register Map - Example with CS1000 and AS1000 sensors The HSI bus addresses for Sensor 1 and Sensor 2 must be different. BeWa CSI-C-11 4548075 from_V250-V253 en-us web 53 / 84...
  • Page 54: Reading Measurement Protocols/Values Via Flumot

    HYDAC sensors into your own user environment / software. To this end, you will have access to all the HYDAC program libraries, a detailed description and help, as well as example programs in various programming languages.
  • Page 55: Method For The Determination Of Contamination Limit Values According To Iso 12669

    7.3 Sending an e-mail notification In addition to the limit value function, the CSI has the option of sending notifications as e-mails. To do this, set up the mail server and the recipient. BeWa CSI-C-11 4548075 from_V250-V253 en-us web 55 / 84...
  • Page 56: Example - E-Mail Settings On The Web Server

    A test e-mail is sent after you confirm the settings with Ok. If the configuration is faulty and the test e-mail cannot be sent, an error code is displayed, see Chapter Troubleshooting/fault rectification [} 64]. 56 / 84 BeWa CSI-C-11 4548075 from_V250-V253 en-us web...
  • Page 57: Open/Operate The Web Interface

    Access is deactivated in the standard settings of your Google Account. 7.4 Open/operate the web interface To operate the CSI-C-11, a comprehensive web interface is available via LAN or a simplified version is available via W- LAN. Find details on this in the subsequent chapters.
  • Page 58: Fig. 20 Web Interface Via Lan

    1. Open the web interface, see Setting the CSI via LAN [} 35] ð The web interface is displayed. 2. Select the required information via the various tabs O Close the web interface by leaving the URL. 58 / 84 BeWa CSI-C-11 4548075 from_V250-V253 en-us web...
  • Page 59: Opening/Displaying/Operating The Web Interface Via Lan

    1. Open the web interface, see Setting the CSI via W-LAN [} 36] ð The web interface is displayed. 2. Select the required information via the various tabs O Close the web interface by leaving the URL. BeWa CSI-C-11 4548075 from_V250-V253 en-us web 59 / 84...
  • Page 60: Sending Measured Data To The Cmx

    HYDAC FILTER SYSTEMS GMBH 7.5 Sending measured data to the CMX The CSI-C-11 can be used as a data source for the HYDAC cloud platform. To do this, the device must be parame- terized with your CMX server and user data.
  • Page 61 CMX server can be accessed by the device. For more information on the HYDAC CMX, visit the website and scan the QR code or visit the URL https://cmx.hydac.com. BeWa CSI-C-11 4548075 from_V250-V253 en-us web...
  • Page 62: Changing The Access Data For The Web Interface And Ftp

    Please note down the password you have created. The password cannot be deactivated or changed without the currently valid password. If you forget your password, the device must be reset to the default settings by the HYDAC service. 62 / 84...
  • Page 63: Performing Maintenance

    HYDAC FILTER SYSTEMS GMBH Performing Maintenance | 8 8 Performing Maintenance The ContaminationSensor Interface CSI is maintenance-free. BeWa CSI-C-11 4548075 from_V250-V253 en-us web 63 / 84...
  • Page 64: Troubleshooting/Fault Rectification

    SMART Sens cation with sensor or Count setting in the Device Settin – Restart the CSI. – Check sensor – Check the wiring. – Check the Error in communi- SMART Sens cation with sensor or Count 64 / 84 BeWa CSI-C-11 4548075 from_V250-V253 en-us web...
  • Page 65 Restart the CSI. the default settings. Error while saving Restart the CSI. the default settings. The log memory is Delete the full. protocols that are no longer necessary from the memory. BeWa CSI-C-11 4548075 from_V250-V253 en-us web 65 / 84...
  • Page 66: Tab. 18 Troubleshooting

    Tab. 18: Troubleshooting Signal light – Evaluating / reading the Error Code To determine the current status of the signal light from the Error Code, mask the particular bits: 66 / 84 BeWa CSI-C-11 4548075 from_V250-V253 en-us web...
  • Page 67: Fig. 23 Signal Light - Evaluating / Reading The Error Code

    – 1.0 ISO class AS, HLB and MCS --> Measured value ≥ 80% of the limit value (3) Red The measured value has exceeded the set limit value (4) Red Measured values not plausible BeWa CSI-C-11 4548075 from_V250-V253 en-us web 67 / 84...
  • Page 68: Disposal/Recycling

    After dismantling and separating all the parts by sorting them correctly, dispose of the product in an environmentally friendly manner. 68 / 84 BeWa CSI-C-11 4548075 from_V250-V253 en-us web...
  • Page 69: A Appendix

    HYDAC SYSTEMS & SERVICES GMBH Friedrichsthaler Str. 15, Werk 13 66450 Neunkirchen - Heinitz Germany Telephone: +49 6897 509 01 Fax: +49 6897 509 324 E-mail: service@hydac.com Homepage: www.hydac.com Tab. 19: HYDAC Service Germany BeWa CSI-C-11 4548075 from_V250-V253 en-us web 69 / 84...
  • Page 70: Finding Accessories

    A | Appendix HYDAC FILTER SYSTEMS GMBH A.2 Finding accessories The following original accessories are available for an optimal system integration of the ConditionSensor Interface CSI-C-11: Double-ended cordset / single-ended cordset The following connection cables for sensors are available: ZBE43 Double-ended cordset, unshielded, black, Socket M12x1, 8-pole, A-coded <->...
  • Page 71 Plug M12x1, 8-pole, A <-> Open cable end, 8–pole Description Part no. Single-ended cordset, L: 2 m, ZBE48S-02 6072261 Line sheath: PUR, color: black, IP67 Single-ended cordset, L: 5 m, ZBE48S-05 6245278 Line sheath: PUR, color: black, IP67 Single-ended cordset, L: 10 m, ZBE48S-10 6072262 Line sheath: PUR, color: black, IP67 BeWa CSI-C-11 4548075 from_V250-V253 en-us web 71 / 84...
  • Page 72 Part no. Connection adapter, 6x, L: 0.15 m, ZBECSI-60 4420372 line sheath: -, color: -, -, for details, see ZBECSI 60 connection adapter - Connection overview [} 74] Power supply unit The following power supply units are available: 72 / 84 BeWa CSI-C-11 4548075 from_V250-V253 en-us web...
  • Page 73: Tab. 20 Power Supply Unit

    HYDAC FILTER SYSTEMS GMBH Appendix | A Length Part no. 1.8 m 3399939 Tab. 20: Power supply unit BeWa CSI-C-11 4548075 from_V250-V253 en-us web 73 / 84...
  • Page 74: Zbecsi 60 Connection Adapter - Connection Overview

    A3 - analog connection, 5-pole Description Description +24VDC Power supply +24 V DC n.c. Not connected Supply voltage GND Signal Analog voltage signal (e.g. 0 … 10 V) n.c. Not connected Tab. 22: A3 - analog connection, 5-pole 74 / 84 BeWa CSI-C-11 4548075 from_V250-V253 en-us web...
  • Page 75 S1 / S2 – HSI SMART Sensor connection, 8-pole Description Description +24VDC Power supply +24 V DC n.c. Not connected Power supply GND n.c. Not connected HYDAC Sensor Interface n.c. Not connected n.c. Not connected n.c. Not connected Tab. 24: S1 / S2 – HSI SMART Sensor connection, 8-pole BeWa CSI-C-11 4548075 from_V250-V253 en-us web 75 / 84...
  • Page 76 Sensor 2 IN ....................Fig. 12 LAN......................Fig. 13 Connection example CSI-C-11-0-0-0 ............Fig. 14 Connection example CSI-C-11 - CS1000 - HDA48x6-A - ETS7246-B ..Fig. 15 Connection example ZBE CSI 60............. Fig. 16 Status LED ....................Fig. 17 Input Register Map - Example with CS1000 and AS1000 sensors ..
  • Page 77 Power supply unit ..................Tab. 21 A1 / A2 - analog connection, 5-pole ............Tab. 22 A3 - analog connection, 5-pole..............Tab. 23 A4 - analog connection, 5-pole..............Tab. 24 S1 / S2 – HSI SMART Sensor connection, 8-pole ........BeWa CSI-C-11 4548075 from_V250-V253 en-us web 77 / 84...
  • Page 78: Glossary

    (predictive maintenance). 78 / 84 BeWa CSI-C-11 4548075 from_V250-V253 en-us web...
  • Page 79 Android various software languages. operating system on the Google Play Store. FluMoS mobile can read sensors via W-LAN or Bluetooth depending on your terminal device. BeWa CSI-C-11 4548075 from_V250-V253 en-us web 79 / 84...
  • Page 80 PCs to be networked. HSI specifies the electrical connection and the type and manner of the binary data transfer of HYDAC sensors. 80 / 84 BeWa CSI-C-11 4548075 from_V250-V253 en-us web...
  • Page 81: Index

    Exclusion of Liability  12 Manufacturer  2 measurement reports Analyzing - see FluMoS  46 FluMoS  47, 54 Reading - see FluMoS  46, 47, 54 Reading via FTP  54 Reading via Modbus  48 Pin assignment BeWa CSI-C-11 4548075 from_V250-V253 en-us web 81 / 84...
  • Page 82 Evaluating the  54 Technical data  20 Electrical data  21 Input data  20 Internal measured data memory  21 Other data  21 Output data  20 Warranty  12 Web interface Login  35 82 / 84 BeWa CSI-C-11 4548075 from_V250-V253 en-us web...
  • Page 84 www.hydac.com...

Table of Contents