13 - STANDARD MAINTENANCE
IMPORTANT:
Never use a pressure water spray without a large diffuser.
Concentrated and/or rotating water jets are strictly forbidden.
Never use a fluid with a temperature above 45 °C to clean the
air-cooled exchangers.
Correct and frequent cleaning (approximately every three
months) will prevent two thirds of corrosion problems. Protect
the electrics box during cleaning operations.

13.7 - Water type heat exchanger

Check that:
- The insulation has not been detached or torn during
operations,
- The heaters and probes are operating and correctly
positioned in their supports,
- The water-side connections are clean and show no sign of
leakage,
- The periodic inspections required by local regulations have
been carried out

13.10 - Refrigerant properties

R32 properties
Relative
Saturated temp.
pressure
-20
306
-19
321
-18
337
-17
354
-16
371
-15
388
-14
406
-13
424
-12
443
-11
463
-10
483
-9
503
-8
524
-7
546
-6
568
-5
591
-4
614
-3
638
-2
662
-1
687
0
713
1
739
2
766
3
794
Saturated temperatures (°C) based on the relative pressure (in kPa)
Relative
Saturated temp.
pressure
4
822
5
851
6
881
7
912
8
943
9
974
10
1007
11
1040
12
1074
13
1109
14
1144
15
1181
16
1218
17
1256
18
1295
19
1334
20
1375
21
1416
22
1458
23
1501
24
1545
26
1635
25
1590
27
1682
13.8 - Variable frequency drive
IMPORTANT: Before any work on the variable frequency
drive, ensure that the circuit is isolated and there is no voltage
present (reminder: The capacitors take approximately
5 minutes to discharge once the circuit breaker has been
opened). Only appropriately qualified personnel are
authorised to work on the variable frequency drive.
In case of any alarm or persistent problem related to the variable
frequency drive, contact the manufacturer's service department.
The variable frequency drives fitted on the units do not require a 
dielectric test, even if being replaced: they are systematically
checked  before  delivery.  Moreover,  the  filtering  components 
installed in the variable frequency drive can falsify the measurement
and may even be damaged. If there is a need to test the insulation
of a component (fan motors and pumps, cables, etc.), the variable 
frequency drive must be disconnected from the power circuit.

13.9 - Refrigerant volume

It is essential to run the unit in cooling mode to find out whether 
the charge is correct; this is done by checking the actual
subcooling.
Following a slight leak, it will be possible to detect a drop in the
refrigerant charge from the initial charge, and this will affect the 
subcooling value obtained at the air-cooled exchanger outlet;
it cannot, however, be detected in heating mode.
IMPORTANT:
it is therefore not possible to optimise the charge in heating
mode following a leak. The unit must be run in cooling mode
if the charge needs topping up.
Relative
Saturated temp.
pressure
28
1730
29
1778
30
1828
31
1878
32
1929
33
1982
34
2035
35
2090
36
2145
37
2202
38
2260
39
2318
40
2378
41
2439
42
2501
43
2565
44
2629
45
2695
46
2762
47
2830
48
2899
49
2969
50
3041
51
3114
Relative
Saturated temp.
pressure
52
3189
53
3264
54
3341
55
3420
56
3500
57
3581
58
3664
59
3748
60
3833
61
3920
62
4009
63
4099
64
4191
65
4284
66
4379
67
4476
68
4575
69
4675
70
4777
85

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents