8 - WATER CONNECTIONS

8.2 - Hydraulic connections

The hydraulic module options are only compatible with closed loops.
The use of the hydraulic module on open systems is prohibited.
Key
Components of the hydraulic module and the unit
1 
Screen filter (particle size of 1.2 mm)
2 
Expansion tank (option)
3
Relief valve
4 
Circulating pump (single or dual)
5
Air vent
6
Water drain tap
7
Pressure sensor
Note: Provides pressure information for the pump inlet (see Control manual)
8
Temperature sensor
Note: Provides temperature information for the water exchanger outlet
(see Control manual)
9
Temperature sensor
Note: Provides temperature information for the water type heat exchanger inlet
(see Control manual)
10 Pressure sensor
Note: Provides pressure information for the water exchanger outlet (see Control 
manual)
11  Check valve (If dual-pump)
12 Plate heat exchanger
13  Heater or heat trace cable for frost protection (Option)
14  Water type heat exchanger flow rate sensor 
15  Water buffer tank module (Option)
Typical hydraulic circuit diagram without the hydraulic module
19
16
23
25
16
19
22
Typical hydraulic circuit diagram with the hydraulic module
17
21
18
20
19
19
16
23
24
16
19
22
21
18
21
18
20
19
13
14
13
T
21
8
2
13
Op�on
1
13
P
7
11
6
4
3
5
15
Op�on
13
25 25
T
13
8
6
23
Installation components
16 Pocket
17 Air vent
18 Flexible connection
19  Shut-off valve
20  800 µm screen filter (mandatory for a unit without a hydraulic module)
21 Pressure gauge
22  Water flow control valve
Note: not required if hydraulic module with variable-speed pump
23 Charging valve
24  Bypass valve for frost protection (if shut-off valves are closed (item 19) during 
winter)
25  Buffer tank (if required)
----  Hydraulic module (unit with hydraulic module option)
Notes:
-
The installation must be protected against freezing.
-
The unit's hydraulic module and the water type heat exchanger may be protected
(factory-fitted  option)  against  freezing  using  electric  heaters  and  heat  trace 
cables (13)
-
The pressure sensors are assembled on connections without Schrader.
Depressurise and drain the system before any work.
12
T
9
13
6
5
12
13
T
9
13
P
10
6
35