5 - PHYSICAL AND ELECTRICAL DATA FOR THE UNITS
For the low pressure dual pump motors of 30RB/RBP 170R-550R units (option 116U)
No.
Description
(2)
(3)
1
Nominal efficiency at full load and nominal voltage
1
Nominal efficiency at 75% of full load and nominal voltage
1
Nominal efficiency at 50% of full load and nominal voltage
2
Efficiency level
3
Year of manufacture
Manufacturer's name and trademark, commercial registration
4
number and head office of manufacturer
5
Product model number
6
Number of motor poles
Nominal shaft power output at full load and nominal voltage
7-1
(400 V)
7-2
Maximum input power (400 V)
8
Nominal input frequency
9-1
Nominal voltage
9-2
Maximum current drawn (400 V) 
10
Nominal speed
11
Product disassembly, recycling or disposal at end of life
Operating conditions for which the motor is specifically designed
I - Altitudes above sea level
II - Ambient air temperature
12
III - Maximum operating temperature
IV - Potentially explosive atmospheres
(1)  Required by regulation No. 2019/1781 concerning the application of directive 2009/125/EC on the ecodesign requirements for electric motors.
(2)  Item number imposed by regulation No. 2019/1781, annex I2b.
(3)  Description given by regulation No. 2019/1781, annex I2b.
(4)  To  obtain  the  maximum  input  power  for  a  unit  with  a  hydraulic  module,  add  the  "maximum  operating  input  power"  for  the  unit  (see  Electrical  data  table)  to  the 
pump power.
(5)  To  obtain  the  maximum  operating  intensity  for a  unit  with  a  hydraulic  module,  add  the  "maximum  operating  intensity"  for the  unit  (see  Electrical  data  table)  to  the 
pump intensity.
(6)  Above 1000 m, a degradation of 3% for each 500 m should be taken into consideration.
(4)
(5)
170R 190R 210R 230R 270R 310R 340R 380R 410R 450R 480R 550R
%
85,9 85,9 86,4 86,4 87,5 87,5 87,5 87,5 89,6 89,6 89,6 89,7
%
86,4 86,4 86,9 86,9 88,2 88,2 88,2 88,2 90,4 90,4 90,4
%
84,9 84,9 85,7 85,7 87,5 87,5 87,5 87,5 89,9 89,9 89,9
-
This information varies depending on the manufacturer and model at
-
the time of incorporation. Please refer to the motor name plates,
-
-
-
kW
1,5
1,5
2,2
2,2
kW
1,76 1,76 2,53 2,53 3,44 3,44 3,44 3,44 4,49 4,49 4,49 6,17
Hz
V
A
3,17 3,17 4,56 4,56 6,33 6,33 6,33 6,33 7,75 7,75 7,75 10,40
r/s
- rpm
Disassembly using standard tools. Disposal and recycling using an
-
m
°C
Please refer to the operating conditions given in this manual or in the
°C
specific conditions given in the selection programs.
-
IE3
Same as above
Same as above
2
3
3
3
3
4
50
3 x 400
48 - 2900
appropriate company
< 1000
(6)
< 40
Non ATEX environment
90
89
4
4
5,5
19

Hide quick links: