Renesas M16C/62P Group Reference Manual page 91

Group renesas embedded application programming interface
Hide thumbs Also See for M16C/62P Group:
Table of Contents

Advertisement

Rev.1.00
2007.11.1
REC10B0002-0100
(Input pin)
Specify one from { RAPI_AN0, RAPI_AN1, RAPI_AN2, RAPI_AN3, RAPI_AN4,
RAPI_AN5, RAPI_AN6, RAPI_AN7, RAPI_AN00, RAPI_AN01, RAPI_AN02,
RAPI_AN03, RAPI_AN04, RAPI_AN05, RAPI_AN06, RAPI_AN07, RAPI_AN20,
RAPI_AN21, RAPI_AN22, RAPI_AN23, RAPI_AN24, RAPI_AN25, RAPI_AN26,
RAPI_AN27, RAPI_INEX0, RAPI_ANEX1 }. The default is RAPI_AN0.
(Operating
Specify one from { RAPI_FAD, RAPI_FAD2, RAPI_FAD3, RAPI_FAD4,
frequency)
RAPI_FAD6, RAPI_FAD12 }. The default value is RAPI_FAD4.
(Resolution)
Specify one from { RAPI_10BIT, RAPI_8BIT }. The default value is
RAPI_8BIT.
(Operating
Specify one from { RAPI_AD_ON, RAPI_AD_OFF }. The default value is
states set)
RAPI_AD_OFF.
Specify one from { RAPI_WITH_SAMPLE_HOLD,
(Conversion
RAPI_WITHOUT_SAMPLE_HOLD }.
method)
The default value is RAPI_WITHOUT_SAMPLE_HOLD.
Specify one from { RAPI_SOFTWARE_TRIGGER,
(Trigger)
RAPI_EXTERNAL_TRIGGER }.
The default value is RAPI_SOFTWARE_TRIGGER.
(External
Specify one from { RAPI_ANEX_UNUSED, RAPI_EXTERNAL_OP_AMP }.
Op-Amp
The default value is RAPI_ANEX_UNUSED.
Connection)
• Specifiable definition values when single sweep mode is used
(RAPI_SINGLE_SWEEP specified)
(Input pin)
Specify one from { RAPI_P0_GROUP, RAPI_P10_GROUP,
RAPI_P2_GROUP }. The default value is RAPI_P10_GROUP.
(Operating
Specify one from { RAPI_FAD, RAPI_FAD2, RAPI_FAD3, RAPI_FAD4,
frequency)
RAPI_FAD6, RAPI_FAD12 }. The default value is RAPI_FAD4.
(Resolution)
Specify one from { RAPI_10BIT, RAPI_8BIT }. The default value is
RAPI_8BIT.
(Operating
Specify one from { RAPI_AD_ON, RAPI_AD_OFF }. The default value is
states set)
RAPI_AD_OFF.
Specify one from { RAPI_WITH_SAMPLE_HOLD,
(Conversion
RAPI_WITHOUT_SAMPLE_HOLD }.
method)
The default value is RAPI_WITHOUT_SAMPLE_HOLD.
Specify one from { RAPI_SOFTWARE_TRIGGER,
(Trigger)
RAPI_EXTERNAL_TRIGGER }.
The default value is RAPI_SOFTWARE_TRIGGER.
(External
Specify one from { RAPI_ANEX_UNUSED, RAPI_EXTERNAL_OP_AMP }.
Op-Amp
The default value is RAPI_ANEX_UNUSED.
Connection)
• Specifiable definition values when repeat sweep mode 0 is used
(RAPI_REPEAT_SWEEP0 specified)
(Input pin)
Specify one from { RAPI_P0_GROUP, RAPI_P10_GROUP,
RAPI_P2_GROUP }. The default value is RAPI_P10_GROUP.
(Operating
Specify one from { RAPI_FAD, RAPI_FAD2, RAPI_FAD3, RAPI_FAD4,
frequency)
RAPI_FAD6, RAPI_FAD12 }. The default value is RAPI_FAD4.
(Resolution)
Specify one from { RAPI_10BIT, RAPI_8BIT }. The default value is
RAPI_8BIT.
89

Advertisement

Table of Contents
loading

Table of Contents