Caution: Removing a sensor for less than 60 seconds does not produce a trouble alarm.
!
Removing or unplugging a sensor for more than 60 seconds or plugging in a different
sensor at any time will cause a trouble alarm.
Host and Node Firmware Requirements
The 4-20mA Bridge requires the following firmware versions in the Host and Node(s) for sensor
compatibility:
IMS-4000 Host
• Input board firmware chip version xx.xx.xx.103 or higher
NOTE: Input board firmware is NOT flash upgradeable. A new firmware chip must be
installed. For information on obtaining a new firmware chip, please contact Sensaphone
Technical Support at 610.558.2700 or via e-mail at support@sensaphone.com.
• ConsoleView version 2.04 or higher
• IMS4K OS version 2.41 or higher
• Voice version 2.09 or higher
*Host version information is viewable through the ConsoleView software on the Version Info
screen and the Help>About selection from the main menu.
IMS-4000 Node
• Firmware version 2.19 or higher.
*Node version information is viewable through the ConsoleView software on the Node
Properties>Diagnostics screen.
Sensor Template (factory default)
Recognition Time:
Specifications
Input Impedance:
IMS Connection:
Operating Temperature Range:
Input Name:
Transducer
3 Seconds
Reset Time:
0 Seconds
Data Logging:
Active
Voice:
None
Input Class:
Other
Input:
4–20mA DC
Current Limit:
50mA
Variable (1000Ω @ 4mA, 260Ω @ 20mA)
Accuracy:
± 0.25%
RJ-45
32–122 deg F (0–50 degC)
Housing:
Black plastic with mounting ears