Configuration

All IMS Solution sensors are auto-configured when you plug them into the Host or Node. When a
new sensor is plugged into the Host or Node, the configuration is set to the factory default via the
Sensor Template. If you have modified these templates, the configuration will be set to the modi-
fied configuration. When a sensor is removed, or the connection is disrupted, the configuration
data remains intact but the sensor will go into trouble status and generate a trouble alarm. When
the sensor is plugged in again, or the connection is re-established, configuration data remains
unchanged and the sensor returns to normal operating condition.
Caution: Removing a sensor for less than 60 seconds does not produce a trouble alarm.
!
Removing or unplugging a sensor for more than 60 seconds or plugging in a different
sensor at any time will cause a trouble alarm.

Sensor Template (factory default)

Recognition Time:

Specifications

Input Name:
Humidity
Low Limit:
20%
High Limit:
60%
60 Seconds
Reset Time:
0 Seconds
Data Logging:
Active
Voice:
humidity.wav
Input Class:
Humidity
Range:
5–95%
Temperature:
32–158º F (0–70º C)
Accuracy:
+/- 3%
Connector:
RJ-45
Housing:
white plastic