Error messages and w
Display
Error messages
SF001
SF022
...
Warnings
GB
SA001
SA004
...
SA021, SA022
SA041 SA042
,
SA051
SA052
SA053
!
Press ESC to correct a parameter value after an error message or after a warning message.
!
Press ENT to ignore a warning message. Setup is coninued. It is recommended to check the entered data.
Error messages and warnings during operation
Display
Error messages
F0102 F0103
,
F0200
F0300
...
F0400 F0403
,
F0500
F0507
...
F0700
F0706
...
F0801 F0804
,
F1100
F1110
...
F1310
F1401
F1407
F1408
Warnings
A0001
A0004
...
A0008 A0010
,
A0080
A0100
A0400
A0800
A1000
A4000
! Press ESC to hide an error message. It it displayed again after 10 seconds.
!
Press STOP to acknowledge an error message or a warning message. Remove the fault.
arnings
during Setup
Fault clearance
Check rated motor values in parameters 370...376. Repeat Setup. Check motor cable
connections and frequency inverter connections.
Check rated motor values in parameters 370...376. Repeat Setup.
The following causes are possible: The motor cable cross-section is not sufficient. The motor
cable is too long. The motor cable is not connected correctly.
Check P372 (rated speed), P375 (rated frequency).
The machine data for star connection is entered, but the motor is connected in delta. For star
connection change the motor cable connection. For delta connection check the entered rated
motor values. Repeat Setup.
The machine data for delta connection is entered, but the motor is connected in star. For delta
connection change the motor cable connection. For star connection check the entered rated
motor values. Repeat Setup.
Check motor connection and frequency inverter connections.
Fault clearance
Frequency inverter overloaded. Check load behavior. Check motor parameter settings.
Overtemperature. Check cooling, fan, sensor and ambient temperature.
Low temperature. Check ambient temperature and electrical cabinet heating.
Motor temperature too high or sensor defective. Check connection on X12.4. Phase failure. Check
motor and wiring.
Overloaded, s
hort circuit or earth fault, motor current or phase failure. C
ramps (P420...P423). C
heck motor and wiring.
DC link voltage too high or too low. Check deceleration ramps (P421, P423) and the connected
brake resistor. Check mains voltage.
Power failure or phase failure, voltage break-chopper or motor-chopper too high. Check mains
voltage, mains fuses and circuit.
Electronics voltage (24 V) too high or too low. Check wiring of control terminals.
Maximum frequency achieved. Check control signals and settings. Check deceleration ramps
(P421, P423) and the connected brake resistor.
Minimum output current. Check motor and wiring.
Reference value signal on input X12.3 faulty, check signal.
Overcurrent on input X12.3, check signal.
Overcurrent on input X12.4, check signal.
Frequency inverter overloaded. Check load behavior. Check motor parameters and application
parameters.
Overtemperature. Check cooling, fan and ambient temperature.
Max. motor temperature reached, check motor and sensor.
Mains phase failure, check mains fuses and supply cable.
Limit frequency reached; output frequency is limited.
Input signal at X12.3 is too low. Increase the value.
Input signal at X12.4 is too low. Increase the value.
DC link voltage has reached the type-specific minimum.
10
heck load behavior and