3. General installation guidelines

3.1 IC-68
Control
ND
• It is recommended to install the unit in a hallway to limit the IC-68
• In order to avoid condensation problems inside the controller, it is recommended to install the
IC-68
on an inside wall. If it is not possible, use spacers to have an air gap between the
ND
wall and the IC-68
ND
• It is required to install the IC-68
• The enclosure is watertight, but not splash proof or immersion proof. DO NOT WATER the
control. Cover it carefully with plastic when cleaning the room.
• The IC-68
should be installed in easy access location but away from damaging elements
ND
(heat, cold, water, direct sunlight, ...).
• It is recommended to punch out knock outs by striking them at the bottom near the back of
the case (see figure 2).
• Do not drill the face, the side, the top or the underside of the control.
• Do not install the IC-68

3.2 Electrical Cables

• All electrical cables must be installed according to local wiring codes.
• All cable shields must be connected to the IC-68
connected to the optional PC interface (see SVPC-40 guide). The shield is needed to protect
the IC-68
and the modules against any electromagnetic interference generated by
ND
lightning or nearby operating machinery.
• Never use the shield as a conductor.
• Connect only one end of the shield to the ground of the IC-68
• Use separate conduit for the low voltage cables (communication and probes) and the high
voltage cables. There must be at least 1 foot (30 cm) between low voltage and high voltage
conduits.
• If a low voltage cable have to cross over a high voltage cable, make this crossing at 90°.
• All cable connections must be soldered or done with approved sealed connectors.
• Probe cables must be 500 ' (150m) or less.
• Communication cables must be 750 ' (250m) or less.
• It is prohibited to use overhead cables outside the building.

3.3 Electrical Power

• Protection from electrical surge should be included in the planning of each installation.
• Every module should have a separate breaker to avoid serious consequences.
• Certain control modules (VSM-2, VSM-2/2, VPM-2, VPM-1 and CIP-1) require the same
phase and same voltage as the IC-68
• It is strongly recommended to have a backup power source to ensure life-sustaining
conditions in case of power failure (see figure 5).
• It is also strongly recommended to put a backup thermostat to sufficient fan and heating
system parallel to the IC-68
• Backup system and alarm must be thoroughly tested and verified as working properly before
using the ventilation system.
IC-68
INSTALLATION GUIDE
ND
.
side up with the cable entry holes facing down (see figure 1).
ND
control near high voltage equipment, power supply or transformer.
ND
to operate.
ND
module output (see figure 6).
ND
www.monitrol.com
's exposure to noxious gases.
ND
power ground only, except for the cable
ND
.
ND
4