3. General installation guidelines

3.1 IC-664 Control

• It is recommended to install the unit in a hallway to limit the IC-664's exposure to noxious gases.
• In order to avoid condensation problems inside the controller, it is recommended to install the
IC-664 on an inside wall. If it is not possible, use spacers to have an air gap between the wall
and the IC-664.
• It is required to install the IC-664 side up with the cable entry holes facing down (see figure 1).
• The enclosure is watertight, but not splash proof or immersion proof. DO NOT WATER the
control. Cover it carefully with plastic when cleaning the room.
• The IC-664 should be installed in easy access location but away from damaging elements
(heat, cold, water, direct sunlight, ...).
• It is recommended to punch out knock outs by striking them at the bottom near the back of
the case (see figure 2).
• Do not drill the face, the side, the top or the underside of the control.
• Do not install the IC-664 control near high voltage equipment, power supply or transformer.

3.2 Electrical Cables

• All electrical cables must be installed according to local wiring codes.
• All cable shields must be connected to the IC-664 power ground only, except for the cable
connected to the optional PC interface (see SVPC-40 guide). The shield is needed to protect
the IC-664 and the modules against any electromagnetic interference generated by lightning
or nearby operating machinery.
• Never use the shield as a conductor.
• Connect only one end of the shield to the ground of the IC-664.
• Use separate conduit for the low voltage cables (communication and probes) and the high
voltage cables. There must be at least 1 foot (30 cm) between low voltage and high voltage
conduit.
• If a low voltage cable have to cross over a high voltage cable, make this crossing at 90°.
• All cable connections must be soldered or done with approved sealed connectors.
• Probe cables must be 500 ' (150m) or less.
• Communication cables must be 750 ' (250m) or less.
• It is prohibited to use overhead cable outside the building.

3.3 Electrical Power

• Protection from electrical surge should be included in the planning of each installation.
• Every module should have a separate breaker to avoid serious consequences.
• Certain control modules (VSM-2, VSM-2/2, VPM-2, VPM-1 and CIP-1) require the same
phase and same voltage as the IC-664 to operate.
• It is strongly recommended to put a backup power source to ensure life-sustaining conditions
in case of power failure (see figure 5).
• It is also strongly recommended to put a backup thermostat to sufficient fan and heating
system parallel to the IC-664 module output (see figure 6).
• Backup system and alarm must be thoroughly tested and verified as working properly before
using the ventilation system.
IC-664 INSTALLATION GUIDE