Ferlux HIDROMATIC Manual page 42

Automatic pellet boiler
Table of Contents

Advertisement

ALARM
DESCRIPTION
CODE
Er09
Low pressure in the water
Er10
High pressure in the water
Er11
Update DATE and TIME
Er12
Power failure
Er15
Power outage
Er16
Communication error
POSSIBLE CAUSE
The working pressure of the
boiler is below 600mbar. (This
error does not appear if the
hydro-stove is on lock or off
and the pump is stopped)
The working pressure of the
boiler is above 2800mbar.
It may appear the first time
the hydro- stove is connected
to the network or after several
days disconnected
IF
THE
BRAZIER
IS PRACTICALLY EMPTY
There is little pellet in the
hopper
A "cave" has formed in the
hopper and the pellet does
not reach the endless
The load auger has been
stuck and/or charging motor
does not rotate
IF THE BRAZIER HAS BEEN
LEFT
FULL OF PELLET (urns burned)
Wet or poor quality pellet
Damaged ignition resistance
and/or connection cable
A power outage has occurred
for a long time while the boiler
was running, or during ignition
There
has
been
communication
between board and screen
42
SOLUTION
Check boiler pressure
If the problem persists for a long
time call the Technical Service
Check the boiler pressure and
check that the circulation pump
is working properly. If this error
persists, notify Technical Service
Update time and day of the week
See section 6.2.3
Reset the error Make sure that the
pellet reaches the endless and / or
throw in case of being
necessary
If after several attempts pellets do
not fall into the burner, notify the
Technical Service
Empty and clean the brazier,
reset the alarm and attempt a
new start
Check the condition and quality of
the pellet
If it does not start after two
or three attempts, notify the
Technical Service
Reset the error and restart.
In case of repeating this alarm
often, or not being able to reset
it, notify the S.A.T. (Technical
Service)
some
Check the cable and connections
failure
to board and display