ALARM
DESCRIPTION
CODE
Er03
Off by smoke temperature
Er04
Off by over water temperature
Off due to excess smoke
Er05
temperature
The plate does not receive a
Er07
signal from the exhaust fan speed
controller
It is not possible to correctly adjust
Er08
the speed of the fan extraction of
fumes
POSSIBLE CAUSE
There is little pellet in the
hopper
A "cave" has formed in the
hopper and the pellet does
not reach the load auger
The load auger has been
stuck
and/or
the
charge
engine does not rotate
There has been a prolonged
power outage
Water
does
not
circulate
correctly
through
installation
Defective
(or
short-circuit)
boiler body probe
The room takes a lot of
temperature and this causes
the smoke temperature of the
boiler to increase
The boiler is very dirty and
this causes it not to have the
necessary exchange for its
correct operation
Missing or damaged smoke
probe.
It could appear sometime due
to fluctuations in the power
grid
The smoke fan and/or any of
its connections are damaged
It could appear sometime due
to fluctuations in the power
grid
Mains voltage is not good or
taken from a non-sinusoidal
alternating current generator
The smoke fan and/or any of
its connections are damaged
41
SOLUTION
Put pellet back in the hopper and
reset the error.
Make sure that the pellet reaches
the auger (undo cave) and pour
pellet into the hopper if necessary.
If after several ignition attempts it
does not fall pellet in the burner,
notify the S.A.T. (Technical
Service)
Check the installation, pumps,
keys, etc.
To remove the error wait for the
boiler to cool and then reset the
the
error. If repeated
often this alarm or does not get it
reset, notify the S.A.T. (Technical
Service)
Check the condition of the boiler
and do cleaning if necessary. In
case of repeating this alarm often
and / or not being able to reset
it, notify the S.A.T. (Technical
Service)
We reset the error and turn it
back on. At this moment this error
disappears and security comes
into operation.
Notify the Technical Service,
meanwhile you can make use of
the boiler.
If this situation re-occurs,
it is advisable to install an
uninterrupted power supply (UPS)
Reset the error and turn it back on
If this situation re-occurs,
it is advisable to install an
uninterrupted power supply (UPS)
Make sure it is connected to a
proper power reset the error and
turn it back on. At this moment
this error disappears and security
comes into operation.
Notify the Technical Service, in the
meantime you can make use of
the device.