Pepperl+Fuchs R2-SP-IC Series Manual page 10

Segment protector
Hide thumbs Also See for R2-SP-IC Series:
Table of Contents

Advertisement

Segment Protector
Product Specifications
Technical Data
Voltage drop main
cable/outputs
Voltage drop trunk In/Out
Terminating resistor
Surge protection
Indicators/operating means
Switch
LED PWR
LED COM/ERR
LED SPURS
Directive conformity
Electromagnetic compatibility
Directive 2004/108/EC
Standard conformity
Electromagnetic compatibility
Degree of protection
Fieldbus standard
Climatic conditions
Shock resistance
Vibration resistance
Ambient conditions
Ambient temperature
Storage temperature
Relative humidity
Shock resistance
Vibration resistance
Corrosion resistance
Mechanical specifications
Connection type
Housing material
Degree of protection
Mounting
Data for application in connection with Ex-areas
EC-Type Examination
Certificate
Group, category, type of
protection, temperature class
Supply
Maximum safe voltage
Outputs
Voltage
10
max. 1.2 V
0 V
external type M-FT 100  +/- 10 %
Trunk overvoltage protection if voltage exceeds typ. 39 V,
max. 41 V
configuration of short-circuit current/rated current
green: Fieldbus voltage > 10 V and fieldbus terminator is
deactivated
yellow: flashing: fieldbus communication status and physical
layer diagnostic status
red: 2 Hz flashing in short-circuit condition
EN 61326-1:2013
NE 21:2011
IEC 60529
IEC 61158-2
IEC 60721
EN 60068-2-27
EN 60068-2-6
-50 ... 70 °C (-58 ... 158 °F)
-50 ... 85 °C (-58 ... 185 °F)
< 95 % non-condensing
15 g 11 ms
1 g , 10 ... 150 Hz
acc. to ISA-S71.04-1985, severity level G3
pluggable , screw terminal or spring terminal
Polycarbonate
IP20
DIN rail mounting
TÜV 12 ATEX 098651 X
II 3 G Ex nAc [ic] IIC T4
35 V
32 V

Advertisement

Table of Contents
loading

Table of Contents