Control drawing / Instruction manual
Segment Protector
R2-SP-IC*
Pepperl+Fuchs GmbH
Lilienthalstrasse 200
68307 Mannheim, Germany
Tel.: +49 621 776-0
Fax.: +49 621 776-1000
Copyright Pepperl+Fuchs, 2017
www.pepperl-fuchs.com
Fieldbus Trunk wiring
R2-SP-IC*
Fieldbus Spur wiring
Model Name
V
/U
oc
0
≤ 32 V
*
V
in
R2-SP-IC*
≤ 32 V
*
V
in
≤ 24 V
*
V
in
*
V
= output voltage of the Fieldbus Power Supply
in
WARNING: Ignition hazard - Switch Position must be set correctly for the intended gas group as specified in the
Fieldbus Spur Wiring Table.
AVERTISSEMENT : Risque d'inflammation – la position du commutateur doit être correctement réglée pour le groupe
de gaz concerné, comme indiqué dans le tableau de câblage des sorties du bus de terrain.
HAZARDOUS (CLASSIFIED) LOCATION
Class l, Zone 2, Groups llB, llA
Class l, Division 2, Groups C, D
(Vin = 9-35 V with Switch in position 2)
Class I, Zone 2, Groups IIC, IIB, IIA
Class I, Division 2, Groups A, B, C, D
(Vin = 9-35 V with Switch in position 1)
Class I, Zone 2, Groups IIC, IIB, IIA
Class I, Division 2, Groups A, B, C, D
(Vin = 9-24 V with Switch in position 2)
①②⑧
Nonincendive
field wiring
apparatus or
HAZARDOUS (CLASSIFIED) LOCATION
intrinsically safe
Class l, Zone 2, Gps. llB, llA; Class II, Zone 22, Gps. IIIC, IIIB, IIIA
apparatus
Class l, Division 2, Gps. C, D; Class II, Division 2, Gps. F, G
(Vin = 9-35 V with Switch in position 2)
Class I, Zone 2, Gps. IIC, IIB, IIA; Class II, Zone 22, Gps. IIIC, IIIB, IIIA
Class I, Division 2, Gps. A, B, C, D; Class II, Division 2, Gps. F, G
(Vin = 9-35 V with Switch in position 1)
Class I, Zone 2, Gps. IIC, IIB, IIA; Class II, Zone 22, Gps. IIIC, IIIB, IIIA
Class I, Division 2, Gps. A, B, C, D; Class II, Division 2, Gps. F, G
(Vin = 9-24 V with Switch in position 2)
Dieses Dokument enthält sicherheitsrelevante Angaben. Es darf nicht ohne Absprache mit dem Normenexperten (NE Ex) geändert werden!
This document contains safety-relevant information. It must not be altered without the authorization of the norm expert (NE Ex) !
CONFIDENTIAL acc. to ISO 16016
Worldwide
Model
V
max
Name
24 V or 32 V
see Fieldbus Spur wiring table
C
/C
a
0
I
/I
[mA]
sc
0
[nF]
65
60
46
60
65
60
Control Drawing
R2-SP-IC*
/V
U
in
m
35 V
L
/L
Switch 1
a
0
[mH]
position
0.25
Position 2
0.125
Position 1
0.25
Position 2
②⑦
Only valid as long as released in EDM
Document No.:116-0406
Edition: 09/2017
UL File Number: E106378
(previously UL File Number E326119)
I
max
Next Segment Protector
≤ 8 A
Gas/Dust groups
IIB/IIA / IIIC/IIIB/IIIA
C, D, F, G
IIC/IIB/IIA / IIIC/IIIB/IIIA
A, B, C, D, F, G
IIC/IIB/IIA / IIIC/IIIB/IIIA
A, B, C, D, F, G
③⑧⑨
Fieldbus Power Supply
with integrated or
external Terminator
date: 2017-Sep-08
or Terminator
116-0406
1
3
sheet
of

Advertisement

loading

Summary of Contents for Pepperl+Fuchs R2-SP-IC Series

  • Page 1 Document No.:116-0406 68307 Mannheim, Germany Edition: 09/2017 Tel.: +49 621 776-0 UL File Number: E106378 Fax.: +49 621 776-1000 (previously UL File Number E326119) Copyright Pepperl+Fuchs, 2017 www.pepperl-fuchs.com Fieldbus Trunk wiring ⑨ Model Name Next Segment Protector 24 V or 32 V ≤...
  • Page 2 ① Nonincendive field wiring apparatus or intrinsically safe apparatus must be suitable for the ambient temperature and be wired and separated in accordance with the wiring methods of National Electrical Code ANSI/NFPA 70, Canadian Electrical Code C22.1 or in accordance with the authority having jurisdiction.
  • Page 3 General requirements: 1. The device must be supplied by a Class 2 or limited-energy source in accordance with UL 61010-1, Third Edition. 2. The device is an OPEN type equipment that must be used within a suitable end-use enclosure. The suitability of the enclosure is subject to investigation by the local authority having jurisdiction at the time of installation.