Control drawing / Instruction manual
Segment Protector
R2-SP-IC*
Pepperl+Fuchs GmbH
Lilienthalstrasse 200
68307 Mannheim, Germany
Tel.: +49 621 776-0
Fax.: +49 621 776-1000
Copyright Pepperl+Fuchs, 2017
www.pepperl-fuchs.com
Fieldbus Trunk wiring
R2-SP-IC*
Fieldbus Spur wiring
Model Name
V
/U
oc
0
≤ 32 V
*
V
in
R2-SP-IC*
≤ 32 V
*
V
in
≤ 24 V
*
V
in
*
V
= output voltage of the Fieldbus Power Supply
in
WARNING: Ignition hazard - Switch Position must be set correctly for the intended gas group as specified in the
Fieldbus Spur Wiring Table.
AVERTISSEMENT : Risque d'inflammation – la position du commutateur doit être correctement réglée pour le groupe
de gaz concerné, comme indiqué dans le tableau de câblage des sorties du bus de terrain.
HAZARDOUS (CLASSIFIED) LOCATION
Class l, Zone 2, Groups llB, llA
Class l, Division 2, Groups C, D
(Vin = 9-35 V with Switch in position 2)
Class I, Zone 2, Groups IIC, IIB, IIA
Class I, Division 2, Groups A, B, C, D
(Vin = 9-35 V with Switch in position 1)
Class I, Zone 2, Groups IIC, IIB, IIA
Class I, Division 2, Groups A, B, C, D
(Vin = 9-24 V with Switch in position 2)
①②⑧
Nonincendive
field wiring
apparatus or
HAZARDOUS (CLASSIFIED) LOCATION
intrinsically safe
Class l, Zone 2, Gps. llB, llA; Class II, Zone 22, Gps. IIIC, IIIB, IIIA
apparatus
Class l, Division 2, Gps. C, D; Class II, Division 2, Gps. F, G
(Vin = 9-35 V with Switch in position 2)
Class I, Zone 2, Gps. IIC, IIB, IIA; Class II, Zone 22, Gps. IIIC, IIIB, IIIA
Class I, Division 2, Gps. A, B, C, D; Class II, Division 2, Gps. F, G
(Vin = 9-35 V with Switch in position 1)
Class I, Zone 2, Gps. IIC, IIB, IIA; Class II, Zone 22, Gps. IIIC, IIIB, IIIA
Class I, Division 2, Gps. A, B, C, D; Class II, Division 2, Gps. F, G
(Vin = 9-24 V with Switch in position 2)
Dieses Dokument enthält sicherheitsrelevante Angaben. Es darf nicht ohne Absprache mit dem Normenexperten (NE Ex) geändert werden!
This document contains safety-relevant information. It must not be altered without the authorization of the norm expert (NE Ex) !
CONFIDENTIAL acc. to ISO 16016
Worldwide
Model
V
max
Name
24 V or 32 V
see Fieldbus Spur wiring table
C
/C
a
0
I
/I
[mA]
sc
0
[nF]
65
60
46
60
65
60
①
⑧
Control Drawing
R2-SP-IC*
/V
U
in
m
35 V
L
/L
Switch 1
a
0
[mH]
position
0.25
Position 2
0.125
Position 1
0.25
Position 2
②⑦
Only valid as long as released in EDM
Document No.:116-0406
Edition: 09/2017
UL File Number: E106378
(previously UL File Number E326119)
⑨
I
max
Next Segment Protector
≤ 8 A
Gas/Dust groups
IIB/IIA / IIIC/IIIB/IIIA
C, D, F, G
IIC/IIB/IIA / IIIC/IIIB/IIIA
A, B, C, D, F, G
IIC/IIB/IIA / IIIC/IIIB/IIIA
A, B, C, D, F, G
⑤
③⑧⑨
Fieldbus Power Supply
with integrated or
external Terminator
date: 2017-Sep-08
or Terminator
⑥
④
⑤
⑩
⑥
116-0406
1
3
sheet
of