Page 1
PROCESS AUTOMATION INSTALLATION AND OPERATION MANUAL 6000 SERIES PURGE/PRESSURIZATION SYSTEM...
Page 2
With regard to the supply of products, the current issue of the following document is applicable: The General Terms of Delivery for Products and Services of the Electrical Industry, published by the Central Association of the Electrical Industry (Zentralverband Elektrotechnik und Elektroindustrie (ZVEI) e.V.) in its most recent version as well as the supplementary clause: "Expanded reservation of proprietorship".
Sequence of events ......................... 23 Turning on power to the enclosure ....................23 Turning off power to the enclosure ....................24 Operation of the 6000 series and component kit ..............25 Operation ............................25 Set-up procedures of 6000 series system ..................29 Operation of the 6000 series system .....................29 Start up label located on 6000 series control unit ...............30...
Page 4
6000 Series Purge/Pressurization System I/O Manual Temperature sensor ........................48 Solenoid ............................49 General specifications ......................50 Certifications ........................... 52 Model number designators ..................... 53 Accessories ..........................54 Appendix ..........................55 Supplement: NFPA 496 information ..................56 Enclosure & device design ......................56 Establishing connection sizes, lengths &...
6000 Series Purge/Pressurization System I/O Manual Safety note and symbols used It is strongly urged that you follow all instructions and recommendations in this manual, in addition to all applicable codes, standards, and local requirements. Failure to do so voids all warranties, both implicit and explicit, and relieves the manufacturer of all liability.
DIN ISO 8573-1 Class 1 to ensure a The user and/ or the installer is obligated to let only trouble free operation of the 6000 Series. competent, trained persons work at the 6000 Control Unit • are familiar with the regulations about safety and...
Page 7
6000 Series Purge/Pressurization System I/O Manual Class Particle Water Size Density Pressure Water Residual oil max in µm max in mg/m dew point in °C content in mg/m content in mg/m 0.01 6.000 7.800 9.400 Subject to modifications without notice...
6000 Series Purge/Pressurization System I/O Manual Certification information Certification markings 6000 Series vent (1 vent or 1st vent when more than 1 vent in use) 6000 Series main unit 6000 Series vent (2nd vent when more than 1 vent in use)
6000 Series Purge/Pressurization System I/O Manual Warning labels WARNING - Conduit seal must be installed within 18 inches of the enclosure. To prevent ignition of flammable or combustible atmospheres, disconnect power before servicing. WARNING - PRESSURIZED ENCLOSURE This enclosure must not be opened unless the area atmosphere is known to be below the ignitable concentration of combustible materials or unless all devices within have been de-energized.
The hazardous area classification can be Class I, Division 1 / Zone 1. The 6000 series operates The 6000 series system can be set up for Class I & II/ Division 1 and Zone 1 & 21 applications in accordance by controlling and monitoring compressed instrument with the NEC-NFPA 70, NFPA496, UL913, CSA C22.2...
6000 Series Purge/Pressurization System I/O Manual Needle valve for pressurization of enclosure (requires flathead screwdriver for adjustment) Manifold for purging and pressurization Manifold with I.S. solenoid valve Connection to protective gas Type 4X (IP66) fittings for supply enclosure flow 316L stainless steel...
6000 Series Purge/Pressurization System I/O Manual Electrical & pneumatic diagrams 12. When removing the pluggable terminal block, it is recommended that the electronics module be 6000 control unit power connections supported by pressing down on top of the EPCU General wiring notes to counter act the lifting force required to remove the connector.
6000 Series Purge/Pressurization System I/O Manual Electrical installation - power and I.S. wiring Prewired IS PWR 1+ IS PWR 1- Temp IS DATA 1A Module IS DATA 1B IS 1 SHLD Prewired IS PWR 2+ IS PWR 2- Power to...
6000 Series Purge/Pressurization System I/O Manual Temperature module connection (when Vent 2 is used) User interface connection (pre-wired) Vent 1 connection Vent 2 connection or Temperature Module connection Inputs 1 - 4, 5.0 V DC I.S. solenoid valve from manifold (pre-wired) I.S.
Page 15
6000 Series Purge/Pressurization System I/O Manual I.S. wiring No wiring is to be in the area between the terminals Non- I.S. wiring EPCU WARNING: To prevent ignition of the flammable Maintain a minimum space of 50.8 mm (2") between the I.S. wiring and the non - I.S. wiring.
0.35" (.889 mm). handle the flow and pressure requirements for purging The 6000 series control unit with the manifold can be and pressurization (see page 66, Establishing connection top, bottom, right, or left hand mounted on the enclosure.
6000 Series Purge/Pressurization System I/O Manual EPV-6000 vent Tools: 1 1/2" NPT knockout ( 50.8 mm [2"] hole ) for Ø vent Vent mounted on the outside of the enclosure Locking nut w/grounding screw (included) Pressurized enclosure Seal gasket (included) Ø 2" (50.8 mm)
6000 Series Purge/Pressurization System I/O Manual 6000 Control unit with housing "WH" Tools: Appropriate sized drill bits or knockout holes 1 1/16" open end box wrench Bolts: 1/4-20 (provided), hole clearance = 6.86 mm (0.27") diameter EFC-6-SS (provided): hole clearance = 15.54 mm (0.61") diameter...
Page 20
6000 Series Purge/Pressurization System I/O Manual Tightening unit cover plate The screws on the unit cover plate must be tightened in the order shown on the diagram to Warning the right. The torque specification on this is 0.113 Nm (1 in-lb). Failure to do so can leave the unit improperly sealed.
6000 Series Purge/Pressurization System I/O Manual 6000 Series Component kit Identification of components User interface Control unit and explosion proof / flameproof enclosure Optional pneumatic manifold with solenoid Component kit Atmospheric reference kit (6000-ACC-514482) for mounting vent inside the enclosure...
6000 Series Purge/Pressurization System I/O Manual Electrical diagrams 12. When removing the pluggable terminal block, it General wiring notes is recommended that the electronics module be supported by pressing down on top of the EPCU For power connections to the control unit and relay...
6000 Series Purge/Pressurization System I/O Manual Electrical installation - power and I.S. wiring Temp User IS Solenoid Module Interface Valve Vents Inputs 1-4 Prewired (BN) (BN) IS PWR 1 Vent 1 (BN) Power to IS PWR 2 EPCU Vent 2...
6000 Series Purge/Pressurization System I/O Manual Component kit installation User interface Panel mount (internal mount, for hazardous area installation, NOT to be used in Dust, Class II/Zone 21 areas) Cable Mounting bracket Customer's nuts ( 4 provided) (provided) enclosure Tighten each to two...
Page 25
6000 Series Purge/Pressurization System I/O Manual External mount (non-hazardous locations only) Customer's enclosure Mounting screws (provided) Cable (provided) User interface (provided) Cut out for M12 connector 16,2 mm Ø (0.64") Environmental ratings are NOT maintained when Mounting in this manner is not approved for mounted in this manner.
Page 26
6000 Series Purge/Pressurization System I/O Manual User Interface mounting template (panel mount) User interface mounting template (external mount) 83.0 mm 16.5 mm 53.5 mm 16.5 mm User (3.25'') (0.65'') (2.10'') (0.65'') interface (reference) ø 3.5 mm (0.15'') ø4.5 mm (0.15'')
6000 Series Purge/Pressurization System I/O Manual Sequence of events Turning on power to the enclosure Door open input off or not used No door open Immediate No immediate shutdown shutdown input off or not used Overload/temp input off or overload/temp...
6000 Series Purge/Pressurization System I/O Manual Turning off power to the enclosure Control power relay input broken/shorted Control power relay Control power relay input Door open input broken/shorted Door open Door open input on Immediate shutdown input broken/shorted Immediate shutdown...
• SMK-600-CK mounting hardware for 6000-UIC-01 relief vent is separate and is mounted to the enclosure. The 6000 series control unit is also available as a kit. The • One 5 m (16.5 ft.), quick disconnect cable for kit consists of the key components of the system, the 6000-UIC-01 control unit, and the user interface.
Page 30
Purge timing EPCU. This allows recalculation of the time based on When using the 6000 series in a gas or gas and dust this measurement. During the dynamic purge time, the location, the time for purging an enclosure can be based...
Page 31
6000 Series Purge/Pressurization System I/O Manual engage the manifold solenoid valve manually when purging and manually disengage when a PRESSURE AS INPUT successful purging is complete. • SA – Semi-automatic mode requires the operator to engage the manifold solenoid valve manually when purging.
Page 32
If using more than one (1) sensor, you may want the M12 (V1) connector and cable that come with the the control action to occur during the peak or vent. If using the 6000 series component kit, the vent is Note average temperature of the sensors.
Please refer to this manual and standards for explanation of requirements. Dust hazardous location 2. Apply power to the 6000 series system. • Enclosure must be cleaned out of all combustible dust. Purging can not be done to clean out 3.
In this application, dust. Refer to "Conditions of Safe Use" Note Start up label located on 6000 series control unit MARKINGS for P/N: 514569 Model 6000 Type X / Ex px 250 CF / 7.2 CM Maximum Enclosure Volume...
SAFE PRESSURE LED (blue) ALARM FAULT LED (red) On: minimum over pressure Blinking: any alarm input detection Solid: 6000 series internal system fault SETUP: to enter setup mode Display: 2 x 20 LCD with backlight screen EXIT: to exit a menu...
6000 Series Purge/Pressurization System I/O Manual Statistics This provides system operating information. These fields are read only. STATISTICS — TEMPERATURES — HUB SENSOR STATS — CURRENT HUB — CURRENT HUB TEMP TEMP XXX °F — MAX HUB TEMP — MAX HUB TEMP XXX °F...
Page 46
6000 Series Purge/Pressurization System I/O Manual — MAX PURGE — MAX PURGE PRESSURE PRESSURE X.XX IN WC — LAST PURGE TIME — LAST PURGE TIME XXXX MIN — MIN PURGE FLOW — MIN PURGE FLOW XX CFM — MAX PURGE FLOW —...
6000 Series Purge/Pressurization System I/O Manual Alarm Fault This provides the reason for the last system alarm. This provides the reason for the system fault. ALARM — NONE FAULT — NONE — NO SAFE PRESSURE — CONTROL OUTPUT 1 —...
6000 Series Purge/Pressurization System I/O Manual Clear statistics CLEAR STATISTICS — CLEAR STATS Y 0R N — SETTING CORRECT Clear fault CLEAR FAULT — CLEAR FAULT Y 0R N — SETTING CORRECT Operation screen This provides the system information. OPERATION —...
6000 Series Purge/Pressurization System I/O Manual System dimensions 6000 series control unit 183.0 mm 32.0 mm (7.20'') (1.25'') 32.0 mm (1.25'') 220.5 mm (8.70'') 183.0 mm (7.20'') Clearance hole for 9/16 - 18 hardware 3 holes Mtg hole for 1/4 - 20 hardware 3 holes 5.0 mm...
6000 Series Purge/Pressurization System I/O Manual 6000 series component kit EPCU with Ex enclosure 3/4" NPT thread #5/16-18 mounting 120.5 mm hardware (4.75'') 3/4''NPT thread 1.3 mm 25.5 mm (1.00'') 51.0 mm 60.5 mm (2.00'') (2.40'') #5/16-18 mounting hardware User interface with mounting bracket (panel mount) 30.0 mm...
6000 Series Purge/Pressurization System I/O Manual User-interface without mounting bracket (external mount) 20.5 mm 83.0 mm 124.0 mm 30 mm (4.90'') (0.80'') (3.25'') (1.20'') Grounding lug (included) #8-32 thread mounting location x 2 62.0 mm 27.0 mm (2.45'') (1.05'') The user-interface can be mounted either...
6000 Series Purge/Pressurization System I/O Manual Temperature sensor 2.0 mm 13.0 mm 10.0 mm 2.0 mm (0.08") (0.50") (0.40") (0.08") 20.0 mm 5.0 mm ø 3.0 mm (0.20") (0.80") (0.10") Subject to modifications without notice Copyright Pepperl+Fuchs Pepperl+Fuchs Group USA: +1 330 486 0002...
6000 Series Purge/Pressurization System I/O Manual Solenoid 22.0 mm 38.0 mm (0.85") (1.50") #1/4 - 20 UNC THD 9.5 mm (0.85") Deep Needle Valve screwdriver slot drive 30.0 mm (1.20") 10.5 mm (0.40") #1/4 - 20 UNC THD 8.0 mm (3.15") deep c'sink 82˚...
General specifications Alarm fault: RED blinking - any alarm input detected Enclosure volume: 7.2 m (250 ft RED solid – 6000 series system fault Number of volume exchange: 4 to 19 I.S. solenoid valve output Refer to drawing 116-013UL-112. Hazardous environment:...
6000 Series Purge/Pressurization System I/O Manual Outlet fitting from manifold: 3/8" bulkhead fitting Parts List (included) Control unit with housing Mechanical specifications (1) 6000 control unit (1) bracket for mounting control unit 6000 control unit (1) EFC-6-SS Protection class (all electronics):...
6000 Series Purge/Pressurization System I/O Manual Certifications Complete Unit Component Kit Class I, Division 1, Groups A, B, C, D T4 Class I, Division 1, Groups A, B, C, D T4 Class I, Zone 1, Groups IICT4 Class I, Zone 1, Groups IICT4...
6000 Series Purge/Pressurization System I/O Manual Model number designators Control unit 6000 - DV - S2 - UN - WH - AC AC - 100 - 250 V AC DC - 20 - 30 V DC WH - with stainless steel housing...
6000-ACC-514480 Mounting bolts for bracket to enclosure and control unit to bracket. 4 pcs. 6000-ACC-514481 3/8" filter and regulator with fitting for connection to 6000 series manifold 6000-ACC-514482 Atmospheric reference kit for mounting EPV-6000-AA vent inside enclosure 1 - 1/2" locknut with ground and gasket for EPV-6000 vent mounted outside enclosure...
6000 Series Purge/Pressurization System I/O Manual Supplement: NFPA 496 information Total Volume Calculation Enclosure & device design 1. The total volume of all pressurized enclosures, Enclosure design requirements devices and wireways must be considered. 1. All windows must be shatterproof and sized as 2.
Page 61
6000 Series Purge/Pressurization System I/O Manual nameplate). Devices may only be accessed after power has been removed and the device has been allowed to cool to a safe temperature, or the area is positively known to be nonhazardous. Subject to modifications without notice...
Need help?
Do you have a question about the 6000 Series and is the answer not in the manual?
Questions and answers