Battery Warning Voltage:
HIGH: High battery warning voltage. The setting range is 14.0V ~ 15.0V.
14.4V is default setting.
LOW: Low battery warning voltage. The setting range is 10.1V ~ 14.0V.
11.4V is default setting. This parameter setting is related to "Shutdown
Voltage" setting. This setting value should be higher than "Shutdown Voltage"
setting.
Shutdown Voltage: If battery voltage is lower than this point in battery mode,
UPS will automatically shut down. The setting range is 10.0V ~ 12.0V.
10.7V is default setting. (The setting is only available for long-run model)
BATT Age: Set up battery age.
Battery Parameter:
Battery AH: setting battery capacity.
• MISCELLANEOUS
Miscellaneous setting page
Auto Restart: (This function is reserved for future use)
Enable: After "Enable" is set, once UPS shutdown occurs due to low
battery and then utility restores, the UPS will return to line mode.
Disable: After "Disable" is set, once UPS shutdown occurs and the utility
restores, the UPS will not automatically turn on
Shutdown Delay Min: UPS will shut down in setting minutes. The countdown
will start after confirming the pop-up screen.
Restore Delay Min: UPS will automatically restart in setting minutes after the
UPS shuts down.
New Password: Set up new password to enter "ADVANCE ► User" menu.
28
3.2.5. Information screen
Touch the icon
to enter information page. Touch the icon
browse information. Touch the icon
icon
to go back to previous menu.
• BASIC information
Basic Information Page1
MCU Version: MCU version.
DSP Version: DSP version.
Serial NO.: The serial number of UPS.
Manufacturer: The information about manufacturer.
Service Contact: The contact name is set in "Basic Setting".
Service Phone: The listed numbers are set in "Basic Setting".
Service Mail: The service email account is set in "Basic Setting".
Basic Information Page2
or
to
to return to main screen. Touch the
29