Gas Pipe Pressure Testing; Sit Valve Description - HAMPTON BAY H35U-NG Owners & Installation Manual

Table of Contents

Advertisement

Gas Pipe Pressure Testing

The appliance must be isolated from the gas sup-
ply piping system by closing its individual manual
shut-off valve during any pressure testing of the
gas supply piping system at test pressures equal
to or less than 1/2 psig. (3.45 kPa). Disconnect
piping from valve at pressures over 1/2 psig.
The manifold pressure is controlled by a regulator
built into the gas control, and should be checked
at the pressure test point.
Note: To properly check gas pressure, both
inlet and manifold pressures should be
checked using the valve pressure ports
on the valve.
1) Make sure the valve is in the "OFF" position.
2) Loosen the "IN" and/or "OUT" pressure tap(s),
turning counterclockwise with a 1/8" wide flat
screwdriver.
3) Attach manometer to "IN" and/or "OUT" pres-
sure tap(s) using a 5/16" ID hose.
4) Light the pilot and turn the valve to "ON" posi-
tion. Read manometer.
5) The pressure check should be carried out with
the unit burning and the setting should be within
the limits specified on the safety label.
Hampton® H35U Direct Vent Freestanding Gas Stove
6) When finished reading manometer, turn off the
gas valve, disconnect the hose and tighten the
screw (clockwise) with a 1/8" flat screwdriver.
Note: Screw should be snug, but not over
tightened.

SIT Valve Description

1) Gas on/off knob
2) Manually Operated Hi/Lo
3) Pilot Adjustment
4) Thermocouple Connection - option
5) Outlet Pressure Tap
6) Inlet Pressure Tap
7) Pilot Outlet
8) Main Gas Outlet
9) Alternative TC Connection Point
installation