WRS Points

The WRS uses the same points as wired room temperature sensors.
Default
Point Name
Point
No.
4
ROOM TEMP
13
RM STPT DIAL
19
DI OVRD SW
21
NGT OVRD
29
DAY.NGT
99
ERROR STATUS
If the TEC application does not use the WRS points, change the point numbers to zero
(0) through the WRS HMI. If the application uses different point numbers, change the
point numbering in the WRS as appropriate.
Revision Date: July 10, 2008
Siemens Building Technologies, Inc.
Table 6. TEC Application Points.
Actual reading from the room temperature sensor.
Temperature setpoint. Default value is 72°F (22°C). (Valid for the full-featured
model only).
Actual status of the override switch. ON indicates that the switch is being pressed.
OFF indicates that the switch is released. (Valid for the full-featured model only).
Indicates the controller operating mode with respect to the override switch. NIGHT
indicates the switch has not been pressed and the override timer is not active. DAY
indicates the switch has been pressed and the override timer is active.
This point is in effect only when DAY.NGT (Point 29) indicates night mode.
Determines the day/night status of the area.
Indicates WRS Low Battery Condition (Bit 3 is set, with a point value of 8) or
Communication Failure (Bit 2 is set, with a point value of 4).
If both conditions exist, the point value will be 12.