● Wiring to Prevent Noise Interference
• Separate input lines and output lines, and use twisted cables.
Noise will be induced on the output lines if they are laid together with or close to input lines.
Incorrect
Binding
• Use short, thick input lines.
Input lines radiate noise, and must therefore be as short and thick as possible.
Incorrect
• Do not loop input or output lines.
Loops in lines can radiate noise to other devices or can function as antennas inducing high-
frequency noise.
Incorrect
• Use short, thick ground wires.
The damping effect of the noise filter built into the Power Supply will be reduced if a long ground
wire is used. Always make ground wires as short and as thick as possible.
Incorrect
• Connect a noise filter.
Include a noise filter on the input side of the Power Supply if faulty operation in electric circuits
connected to the output from the Power Supply are being caused by sources of surge on the AC
input line, such as large magnetic relays.
Ground the noise filter with a thick, short wire.
Incorrect
Noise
• Use shielded cables for the remote sensing and remote control signal lines.
Remote sensing and remote control signal lines must always be wired separately using shielded
cables to prevent faulty operation caused by the induction of noise. Noise can be induced when
these signal lines are laid together with input lines or power lines, which often carry noise.
Incorrect
Binding
Correct
Correct
Correct
Correct
Correct
Noise filter
Ground
Correct
Power Supply