Power Supply Precautions for Correct Use
■Installation
● Mounting Methods
The standard mounting methods should
be used to ensure proper heat
dissipation. If other mounting methods
must be used, the ambient temperature
must be lowered or the load rate must
be reduced to prevent temperature
increase inside the Power Supply
caused by poor heat dissipation.
Refer to the information in the table on
the right.
● Installation Space
When mounting two or more Power
Supplies side by side, be sure to provide
spacing between them as indicated in
the table on the right or greater.
A
A
B
C
B
C
S82J
Note. Be sure to provide an installation space that
allows for shielding (including ducts).
DIN-rail Mounting Models: Main Models
Mounting direction
Standard
Model
S82K
OK
S8TS
OK
S8VS(15, 30W)
OK
S8VS (60, 90, 120,
OK
180, 240 W)
S8T-DCBU-01
OK
S8T-DCBU-02
OK
S8VM
OK
Screw Mounting Models: Main Models
Mounting direction
Standard
Model
S82J
Yes
S8VM
Yes
*1. The 300-W model can be used under given
conditions.
*2. The 600-W model can be used.
Spacing Required Between Power Supplies
Model
S82J
S82K
S8VS
S8VM
* Ambient temperature of 50° C: 100 mm
Power Supply
Horizontal
Face-up
No
Conditional
No
No
No
OK
No
No
No
No
No
No
No
No
Horizontal
Face-up
Face-down
Yes *1
Conditional *2
Conditional *2
Yes
Yes
Yes: Can be used
No: Cannot be used.
Conditional: Can be used at an ambient tempera-
ture of 50° C (up to 50% of load rate).
Dimension A
Dimension B
20
20 (300, 600 W)
10
---
20
---
20
---
Technical Information
Face-down
No
No
No
No
No
No
No
Horizontal
No
No
No
(Unit: mm)
Dimension C
20 (300, 600 W)
---
---
---
9

Advertisement

loading

This manual is also suitable for:

S82jS8tsS8vsS8vm