Technical Manuals Online! - http://www.tech-man.com
Menu:Maint:Control:Disarm
PHY:FireFinder@1, DLC@1, HFP11@2
DISARM OUTPUTS
AT: FireFinder@1, DLC@1, HFP11@2
COMPONENTS: Relay 1
OUTPUT:
De-Energized
Cancel
Settings
Figure 3-10
Disarm Outputs Status Screen
At this point, the components that were selected are not yet disarmed.
Press the Execute soft key to disarm the selected components.
When the devices are disarmed, a trouble reports on the system indicating exactly
what has been disarmed and the Partial System Disable LED glows steady yellow.
Navigate to the desired device using the More Info +/- buttons, select the Control
option by pressing the Control soft key and then Touch the box labeled Arm.
The Arm Devices screen displays showing the location (In this example, AT:
FireFinder@1, DLC@1, HFP11@2). See Figure 3-11.
Menu:Maint:Control:Arm
PHY:FireFinder@1, DLC@1, HFP11@2
ARM DEVICES
AT: FireFinder@1, DLC@1, HFP11@2)
Category text information
10:53
Cancel
Settings
Figure 3-11
Arm Devices Screen
To arm all elements associated with the device, press the Execute soft key.
To select individual components associated with the device, press the Settings soft key.
Touch the desired Devices, Inputs or Outputs box to select it. See Figure 3-12. This
screen is context-sensitive and will allow you to select only those items which are
applicable. (If you select the wrong item, touch the box you wish to select.)
firealarmresources.com
PMI OPERATION MANUAL
Execute
Execute
MAINTENANCE MODE
3-7