Appendix K
K: MJ-5 Operating Procedures
Use the following instructions as a quick reference for
performing many of the standard MJ-5 operating
procedures.
View Instantaneous Load Voltage (Vld)
1.
Press Menu key twice
2.
Press Down Arrow once
3.
Read voltage (Vld) on display
View/Set Forward Voltage Level Value
1.
Press Voltage Level Fast-Path key
2.
Read Voltage Level on display
3.
Press Change/Save key - right hand digit will flash
4.
Press Left Arrow key to move left on display or Right
Arrow key to move right on display
5.
Press Up/Down Arrow key to increase or decrease
desired voltage on display - flashing digit will change
6.
Press Change/Save key again to save the new Voltage
Level
View/Set Bandwidth Value
1.
Press Bandwidth Fast-Path key
2.
Read Bandwidth on display
3.
Press Change/Save key - right hand digit will flash
4.
Press Left Arrow key to move left on display or Right
Arrow key to move right on display
5.
Press Up/Down Arrow key to increase or decrease
desired bandwidth on display - flashing digit will
change
6.
Press Change/Save key to save the new Bandwidth
setting
View/Set Time Delay Value
1.
Press Time Delay Fast-Path key
2.
Read FWD time delay on display. For REV time delay
press the Time Delay button again.
3.
Press Change/Save key - right hand digit will flash
4.
Press Left Arrow key to move left on display or Right
Arrow key to move right on display
5.
Press Up/Down Arrow key to increase or decrease
time delay on display - flashing digit will change
Siemens Industry, Inc.
:
MJ-5 Operating Procedures
6.
View/Reset Max/Min Values
1.
2.
3.
4.
View/Set Line Drop Compensation Values
1.
2.
3.
4.
5.
6.
7.
8.
9.
10. Press Reactance Fast-Path key
11. Read the Forward reactive compensation voltage (X)
12. Repeat steps 3 to 6 above to set the Forward reactive
13. Press Reactance Fast-Path key again
14. Read Reverse reactive compensation voltage (X) on
15. Repeat steps 3 to 6 above to set the Reverse reactive
View Operation Counter Values
1.
Press Change/Save key to save the new time delay
value
View Meter value or tap position
Press Max/Min key once
Read maximum and minimum values on display
To reset maximum and minimum values on display,
press Cancel Reset key once
Press Resistance Fast-Path key
Read resistive compensation voltage (R) on display
Press Change/Save key - right hand digit will flash
Press Left Arrow key to move left on display or Right
Arrow key to move right on display
Press Up/Down Arrow key to increase or decrease
compensation voltage on display - flashing digit will
change
Press Change/Save key to save the new resistive
compensation voltage value
Press Resistive Fast-Path key again
Read Reverse resistive compensation voltage (R) on
display
Repeat steps 3 to 6 above to set the resistive
compensation voltage
on display
compensation voltage
display
compensation voltage
Press Operation Counter Select Fast-Path key (Op
Count)
76