System Blocking Design - ABB RELION REB500 Operation Manual

Distributed busbar protection
Hide thumbs Also See for RELION REB500:
Table of Contents

Advertisement

1MRK 505 400-UEN B
Signal
42805_ Check Zone Bypassed
42810_Check_Zone_Diff_Alarm
43305_BFP trip t1
43310_BFP trip t2
43405_BFP blocked
44305_EFP trip
44405_EFP blocked
45305_OCDT trip
45405_OCDT blocked
45805_OCDT start
46705_DR general started
47305_PDF Trip
47405_PDF blocked
48805_Voltage criterion
49405_BP blocked
49410_BP partial blocked
The following signals (in
the central unit:
41305_Trip BB zone
41815_Diff. current alarm
42305_BBP trip
42330_Check_Zone_Operated
46705_DR general started
3.6

System blocking design

Certain central and bay unit input signals can directly influence the output signals.
shows the blocking system. The numbered items describe:
Distributed busbar protection REB500
Technical manual
Description
The check zone release function for BBP is bypassed.
The differential currents of the check zone exceed the set alarm level.
BFP tripped in time step 1.
BFP tripped in time step 2.
BFP is blocked (either a bay unit or the entire system).
EFP has tripped.
EFP is blocked (either a bay unit or the entire system).
OCDT has tripped.
OCDT is blocked (either a bay unit or the entire system).
One of the feeder time-overcurrent functions has picked up.
This signal must be configured in the central unit and defined as a DR
trigger, so that the DR function of the central unit is basically able to be
started by the following input signals for general start of DR:
36705_General Start DR
16750_Start DR_10 or 16760_BP General Start DR
Without this signal, the central unit will not respond to a General Start DR.
Signals tripping by PDF.
PDF is blocked (either individual bays or the entire system).
UV has been activated (either individual bays or throughout the system).
The outputs of the bay protection functions are blocked (either individual
bays or throughout the system).
Certain bay protection output signals in specific bays or throughout the
entire system are blocked (Must be configured together with the
corresponding BU output signal 29410_BP partial blocked).
Table 18
and
Table
19) can be used to trigger a disturbance record in
© Copyright 2019 ABB. All rights reserved
This output signal is also used as an indication, that a
general start of all appropriately configured fault
recorder has taken place in the system.
Section 3
Signals
GUID-F331F75E-13B4-4577-AC3C-592437194D17 v2
Figure 1
19