Section 6
Additional protection options
IEC18000336 V2 EN-US
Figure 10: Block diagram of BFP (logic type 1)
6.1.2
Configuration
BFP has two adjustable timers. At the end of time t1, a second attempt is made to trip the
breaker that has failed to trip; at the end of time t2 the surrounding breakers are tripped. A
42
© Copyright 2019 ABB. All rights reserved
1MRK 505 400-UEN B
GUID-D6AB3AA3-F1C3-41E7-A08A-585F8D60A742 v2
Distributed busbar protection REB500
Technical manual