ABB RELION REB500 Operation Manual page 59

Distributed busbar protection
Hide thumbs Also See for RELION REB500:
Table of Contents

Advertisement

1MRK 505 400-UEN B
Signal "17610_PDF ext release" configured?
IEC18000306 V1 EN-US
Figure 20: Block diagram of breaker pole discrepancy protection
To verify a pole discrepancy, the current criteria and the condition of the circuit-breaker
auxiliary contacts must be taken into account (external plausibility check).
that the output signal of the function is enabled by the binary input 17610_PDF ext release.
If the input 17610_PDF ext release is not configured, the function is enabled by default.
The breaker pole discrepancy protection does not intertrip the respective busbar zone.
 
17610_PDF ext release
L
            L
1
L
           L
1
IEC18000339 V1 EN-US
Figure 21:
Distributed busbar protection REB500
Technical manual
I
< pd
* I
set
max
I
max
I
< pd
* I
set
max
(greatest of
I
< pd
* I
I
, I
, I )
set
max
L3
L1
L2
I
> I
max
mset
17610_PDF ext release
&
17205_Block PDF
1
37205_Block PDF
∆pd
:
Pole discrepancy factor (for example, 0.6 × I
set
I
:
Pole discrepancy setting (for example, 0.2 × I
mset
 
           L
           CB CLOSE signal
2
3
           L
           CB OPEN signal
2
3
+
 
14000032-IEC18000339-1-en.vsd
External plausibility check
Under certain conditions, the breaker at the remote end or possibly some other
breaker may be involved without a plausibility check.
© Copyright 2019 ABB. All rights reserved
PDF timer
1
t
0
&
1
PDF blocked
 
Additional protection options
27805_PDF start
27305_PDF
Trip
47305_PDF
Trip
&
27105_PDF
TRIP
27405_PDF blocked
12000182-IEC18000306-1-en.vsd
)
max
)
N
Figure 20
shows
Section 6
53

Advertisement

Table of Contents
loading

Table of Contents