ABB RELION REB500 Operation Manual page 21

Distributed busbar protection
Hide thumbs Also See for RELION REB500:
Table of Contents

Advertisement

1MRK 505 400-UEN B
Signal
23340_BFP TRIP L0
23405_BFP blocked
24105_EFP REMOTE TRIP
24305_EFP trip
24405_EFP blocked
24805_EFP start
25105_OCDT TRIP
25305_OCDT trip
25405_OCDT blocked
25805_OCDT start
27105_PDF TRIP
27305_PDF trip
27405_PDF blocked
27805_PDF start
Table 13:
Signal
26805_DR ready
26810_DR memory full
26815_DR recording
26820_DR record available
Table 14:
Signal
28805_Voltage criterion
Table 15:
Signal
29405_BP blocked
29410_BP partial blocked
29600 ParaSet_1 active
29605 ParaSet_2 active
29610 ParaSet_3 active
29615 ParaSet_4 active
BP output signals available for
configuration
Distributed busbar protection REB500
Technical manual
T
L
BU output signals for disturbance recorder (DR)
BU output signals for voltage release (UV)
Description
The voltage release criterion of this bay unit is fulfilled (measuring voltage
is below the setting of the voltage criterion).
BU output signals for bay protection (BP) (REB500sys only)
Description
The outputs of the bay protection functions are blocked (either the bay
concerned or throughout the system).
Certain bay protection functions are blocked (Signal must be set explicitly
by the bay protection).
Parameter set 1, 2, 3, or 4, respectively, is active. This can take place via the
station bus or an input signal.
In addition to the bay protection output signals listed above, which are
always available, use can also be made of the signals configured for the
binary signal output block of the bay protection. The number of these
signals depends on the protection functions and signals included in the
bay protection.
© Copyright 2019 ABB. All rights reserved
#
Description
2
BFP detected a fault on neutral system (L0) and has
tripped.
1
BFP is blocked (either the bay or the whole system).
2
Tripping command issued by EFP.
1
EFP has tripped.
1
EFP is blocked (either the bay or the whole system).
1
EFP has started.
2
Tripping command issued by OCDT.
1
Signals tripping by OCDT.
1
OCDT is blocked (either the bay or the whole system).
1
OCDT has started.
2
Tripping command by PDF.
1
Signals tripping by PDF.
1
PDF is blocked (either the bay concerned or the entire
system).
1
PDF has started.
Description
DR is standing by.
DR memory is full.
DR is in the process of recording.
Disturbance records are available.
Section 3
Signals
15