Section 3
Signals
3.7.2
Tripping commands automatically combined by the system
The individual tripping commands of the station protection functions are assigned to the
respective combined tripping commands automatically by the system. The same applies for
the default tripping commands of the bay protection:
•
29110 BP TRIP
•
29115 BP TRIP L1
•
29120 BP TRIP L2
•
29125 BP TRIP L3
•
29130 BP REMOTE TRIP
For details about the automatically combined tripping logic see
3.7.3
User defined combined tripping (integration of bay
protection)
The individual tripping commands of the bay protection functions can be assigned to the
default tripping commands (list see under
HMI500 menu Settings/Bay Protection/Configuration/Configuration-Select Protection
Function/Trip Logic/Logic Mode: OR.
For details about user defined tripping combinations logic see
26
Section
© Copyright 2019 ABB. All rights reserved
GUID-1B983EB8-6E17-449A-B0B3-4A39476697E2 v1
Table
23.
GUID-D9CC4580-3CB7-4CC4-9836-83C99433B617 v1
3.7.2) by using an OR-Logic (see under the
Table
23.
Distributed busbar protection REB500
1MRK 505 400-UEN B
Technical manual