Binary Inputs On Bay Units - ABB RELION REB500 Operation Manual

Distributed busbar protection
Hide thumbs Also See for RELION REB500:
Table of Contents

Advertisement

Section 3
Signals
Digit 1
Category
4
Output on Central
unit
5
System Signal
Table 4:
Signal type
Signal Input
Signal Output
Direct tripping
signals
Input signals
that can initiate
tripping
Output signals
used for
transfer tripping
Following sections list binary input and output signals on bay units and central units. All
signals are listed in ascending order of their numbers in their respective filter groups.
3.2

Binary inputs on bay units

Table 5:
Signal
11105_External TRIP
11110_External TRIP BB zone
11115_Ext_Test_TRIP
Table continues on next page
8
Digit 2
Protection function
3
BFP
4
EFP
5
OCDT
6
DR
7
PDF
8
UV
Signal text nomenclature
Nomenclature
[Effect] [Function] [Phase] [Order]
For example,
Start BFP L1 1
Block BFP
[Function] [Effect] [Phase] [Order]
For example, BFP Trip L1
[Function] [TRIP] [Phase] [Order]
For example,
BFP TRIP
SSS TRIP L1
[Origin] [Location]
For example, Ext TRIP BB-Zone
[Function] [Target] [TRIP]
For example, BBP Remote TRIP
BU general input signals
© Copyright 2019 ABB. All rights reserved
Digit 3
Signal function
4
Blocking Signal
5
Bus image
6
Control
7
Start
8
General Alarm
Upper and lower case rules
[Effect] First letter upper case, other letters
lower case.
[Function] All letter upper case.
[Phase] [Order] Conform to national upper and
lower case conventions.
[Effect] First letter upper case, other letters
lower case.
[Function] All letter upper case.
[Phase] [Order] Conform to national upper and
lower case conventions.
[Function] All letter upper case.
[Phase] [Order] Conform to national upper and
lower case conventions.
no explicit rule
[Function] All letter upper case.
[Target] First letter upper case, other letters
lower case.
Description
Tripping command received from another protection
device(including one in the remote station) and used for the
REB500 tripping contact to trip faults on a line or a power
transformer.
Used when an external signal has to trip the entire bus zone to
which the feeder is connected (for example, an external BFP signal).
Applied to all the bay units of the bus zone and sections of busbars
interconnected by an isolator (intertripping).
Activates the signal 21120_EXT_TEST_TRIP to operate several
tripping relays simultaneously.
1MRK 505 400-UEN B
Digit 4, 5
Sequence number
20
and so on
GUID-D6989DA8-87EC-4663-9F09-7327E736720E v2
Distributed busbar protection REB500
Technical manual