Section 5
Busbar protection
IEC18000459 V1 EN-US
Figure 8:
The setting for the differential current alarm is entered as a percentage of the minimum fault
current setting
setting is 5%.
Should the differential current alarm pick up, alarm is not actually given until the set time delay
has expired. A typical setting is 5s.
5.2

Tripping logic

I > I
diff
k=

IEC18000272 V1 EN-US
Figure 9:
40
Settings/Busbar protection - Operating characteristics
IKmin . The alarm should be set lower than the lowest load current. A typical
Nothing has to be configured in HMI500 for the phase comparison algorithm.
The settings for this function are determined when engineering the scheme for
a particular application. The parameters involved are the operating angle ⱷ
and the two minimum current settings (L1, L2, L3 and L0) for the inclusion of a
feeder in the evaluation.
diff set
I
diff
> k
I
set
restr
set
Busbar protection tripping logic
© Copyright 2019 ABB. All rights reserved
&
Trip
12000055-IEC18000272-1-en.vsd
Distributed busbar protection REB500
1MRK 505 400-UEN B
12000132-IEC18000459-1-en.vsdx
GUID-159F91B2-F393-4682-A62A-4481F24E4BEB v1
Technical manual
max