Section 2 Installation

Configuring the APS-6R

The APS-6R may be configured for the following:
The figure below illustrates the location of the jumpers:
18
www.PDF-Zoo.com
• 8-hour delay for reporting loss of AC: cut jumper JP2.
• 16-hour delay for reporting loss of AC: cut jumper JP2 and JP3.
• 240 VAC operation: See WARNING below. Cut jumper JP1
before applying power.
WARNING: HIGH VOLTAGE!
Cut JP1 before applying power
for 240 VAC operation.
Figure 9 Configuring the APS-6R
firealarmresources.com
JP3
JP1
JP2
PN 50702:B2 4/14/03