Appendix G Nfs-3030; Mounting An Aps-6R In A Chassis; Connecting To The Amps-24 And Cpu-3030 - Notifier APS-6R Instruction Manual

Auxiliary
Hide thumbs Also See for APS-6R:
Table of Contents

Advertisement

APPENDIX G - NFS-3030
APPENDIX G - NFS-3030

Mounting an APS-6R in a Chassis

An Auxiliary Power Supply is mounted on a CHS-4 Series chassis.
See "Mounting in CAB-3/CAB-4 Series Cabinets" on page 12..

Connecting to the AMPS-24 and CPU-3030

Make the following connections as shown in the figure below.
J9
J2
TB2
JP2
JP3
To battery
backup
Figure 19 Wiring to AMPS-24 and CPU-3030
28
www.PDF-Zoo.com
• Connect primary power from TB1 on the APS-6R to TB3 HOT,
NEUT and EARTH on the AMPS-24.
• Connect secondary power from TB3 BATT(+) and BATT(-)on
the APS-6R to TB5 (BAT IN +) and TB4 (BAT OUT-)
respectively on the AMPS-24.
• Connect trouble input from J3 on the APS-6R to the J5 Trouble
bus connection on the CPU-3030.
J1
J3
TB3
TB1
-
+
firealarmresources.com
CPU-3030
AMPS-24
PN 50702:B2 4/14/03