Appendix D System 500; Mounting An Aps-6R In A Cab-500 Backbox; Connecting The Aps-6R To An Mps-24Brb - Notifier APS-6R Instruction Manual

Auxiliary
Hide thumbs Also See for APS-6R:
Table of Contents

Advertisement

APPENDIX D - System 500

Mounting an APS-6R in a CAB-500 Backbox

Connecting the APS-6R to an MPS-24BRB

J9
J2
TB2
JP2
JP3
PN 50702:B2 4/14/03
www.PDF-Zoo.com
An Auxiliary Power Supply is mounted in the same way as the AFP-
400, see Appendix B.
Make the following connections as shown in the figure below.
• Connect primary power from TB1 on the APS-6R to
MPS-24BRB terminal block TB1, Pin 3(
• Connect secondary power from TB3 on the APS-6R to
MPS-24BRB terminal block TB3, Pin 1(+) and Pin 2(–).
• Connect trouble input from J3 on the APS-6R to MPS-24BRB
terminal block P4.
J1
J3
-
+
To battery backup
Figure 16 Wiring to MPS-24BRB
firealarmresources.com
APPENDIX D - System 500
TB1
EARTH
R55
AC NEUT
AC HOT
1 2 3 4 6 7 8
P2
CB1
2
3
4
P1
7
5
3
2
1
MPS-24BPCC
REV ___
) and Pin 4(
NEUT
HOT
+24 VRESET
COMMON
+24 VPOWER
COMMON
BATT +
BATT -
1
2
1
2
3
4
TB2
TROUBLES
AC
BATT
+EF
-EF
JP3
).
TB3
P3
P4
25

Advertisement

Table of Contents
loading

Table of Contents