Section 2 Installation
.
J9:Output Circuit 3 - Non Power-limited, 6 A @24 VDC (+10, –15%)
- +
- + - +
J9
J2
TB2
JP2
JP3
14
www.PDF-Zoo.com
J2:Output Circuit 2
J1:Output Circuit 1
J1
+
TB2:
Output Circuit 1
+
TB2:
Output Circuit 2
J3
Trouble Bus In/Out
TB3
BATT (+)
BATT (–)
HOT
NEUTRAL
EARTH
TB1
Figure 5 Typical Wiring for an APS-6R
firealarmresources.com
Output Circuit 1
(J1 and TB2):
Power-limited
3 A @24 VDC
(+10, –15%)
TB3 - Secondary Power: 24 VDC batteries.
(
Refer to the caution above this illustration
about secondary power and supervision)
TB1 - Primary Power:
120 VAC or 240 VAC.
Earth Ground - Connects to chassis or
ground terminal on main power supply. If 2 or
more units are connected, secondary units
connect to earth ground on the previous
APS-6R in the chain.
Output Circuit 2
(J2 and TB2):
Power-limited
3 A @24 VDC
(+10, –15%)
See Page 18 in
"Configuring the
APS-6R".
EARTH
PN 50702:B2 4/14/03