APPENDIX F - NFS-640

Mounting an APS-6R in a Chassis

Connecting the APS-6R to an NFS-640

J9
J2
TB2
JP2
JP3
PN 50702:B2 4/14/03
www.PDF-Zoo.com
An Auxiliary Power Supply is mounted on a CHS-4 Series chassis.
See "Mounting in CAB-3/CAB-4 Series Cabinets" on page 12..
Make the following connections as shown in the figure below.
• Connect primary power from TB1 on the APS-6R to TB2 HOT
NEUTRAL and EARTH on the NFS-640.
• Connect secondary power from TB3 on the APS-6R to TB1 on
the NFS-640, BATT- and BATT+.
• Connect trouble input from J3 on the APS-6R to J11 on the
NFS-640.
J1
J3
TB3
TB1
-
+
To battery backup
Figure 18 Wiring to the NFS-640