APPENDIX A - AFP-200
APPENDIX A - AFP-200

Mounting an APS-6R to an AFP-200 Backbox

The Auxiliary Power Supply is mounted in the bottom of the backbox.
Note: If an APS-6R is installed in the backbox, the batteries must be
installed in a separate battery box, such as the BB-17. The battery box
must be located within 20 feet (6 meters) of the enclosure containing
the control panel and all connections must be contained in conduit.
To mount the APS-6R, follow these instructions:
Step
Action
1
Remove plastic cover from APS-6R.
2
If 240 VAC is to be used, cut JP1 jumper at this time. See
instructions and high voltage warning on Page 18 in "Configuring
the APS-6R".
3
Locate the mounting holes in the AFP-200 backbox. Insert a self-
tapping screw through each of the APS-6R mounting slots.
4
Position the APS-6R in line with the holes in the AFP-200 backbox;
then, thread the self-tapping screws until the APS-6R is securely
fastened to the AFP-200 backbox.
6
Reinstall the plastic chassis cover.
APS-6R
Assembly
Figure 11 Mounting the APS-6R to an AFP-200 Backbox
20
www.PDF-Zoo.com
AFP-200
Backbox
firealarmresources.com
Self-tapping screws
(2 places)