Section 3 Configuring The Acps-2406; Dip Switch Configuration - Notifier ACPS-2406 Manual

Addressable charger
Hide thumbs Also See for ACPS-2406:
Table of Contents

Advertisement

Configuring the ACPS-2406

Section 3 Configuring the ACPS-2406

3.1 DIP Switch Configuration

Programming at the ACPS-2406 is done by configuring two sets of DIP switches, SW2 and SW3. SW3 is
a set of mode selection switches for output circuits one through four, as well as AC Loss, AC Delay, settings
for coded NAC patterns, Canadian Trouble Reporting, and Dual Stage operation. SW2 is a set of switches
with various mode options for the output circuits, as well as settings for Signal Silence, strobe
synchronization type, and battery charger. Setting these 16 switches in different configurations will provide
various options as described in Table 3.1.
SW2 and SW3 are horizontally aligned on the ACPS-2406 board just above the metal case which
covers the bottom half of the power supply. To place a switch in the OFF position, depress the end
of the switch closest to the metal case. To place a switch in the ON position, depress the end of the
switch farthest from the metal case. Refer to Figure 3.1 below for an illustration of the OFF and
ON positions. Table 3.1 describes the ACPS-2406 DIP Switch settings.
Switch 1 is OFF. The
end of the switch near the
metal case has been
depressed.
Note: DIP Switch settings should be changed only while the ACPS-2406 is powered down.
16
SW2
OP TION S
1
2
3
4
5
6
7
8
1
2
3
4
5
Metal
Case
O FF 1
2
3
4
5 6
Figure 3.1 Setting a DIP Switch
DIP Switch Configuration
SW3
OP TION S
6
7
8
7
8
Switches 2 through 8 are
ON. The end of the
switch farthest from the
metal case has been
depressed.
ACPS-2406 PN 51304:B 09/02/2003