Notifier APS-6R Instruction Manual page 8

Auxiliary
Hide thumbs Also See for APS-6R:
Table of Contents

Advertisement

Section 1 Overview
Three 24 VDC output circuits
One (1) non power-limited
Two (2) power-limited
(Refer to Figure 5 on page
page 14 for more specific
information on output circuits)
Fuse F2 for battery protection
(10A, 3AG, slow blow)
Fuse F1 for AC protection
(4A, 3AG, slow blow)
Jumper JP1 for selecting AC input voltage
(120 VAC default). See Page 18 in "Configuring the APS-6R".
WARNING: HIGH VOLTAGE.
cut JP1 before connecting power.
8
www.PDF-Zoo.com
The figures below identify the features of the APS-6R power supply:
Figure 2 APS-6R Control Board
Figure 3 APS-6R Main Board
firealarmresources.com
Trouble In (J4) - Trouble Out (J3)
"P" style connectors for internal cabinet
connections
LED Status Indicators:
Green LED – Indicates AC power on
Yellow LED – Indicates loss of AC or
battery
Jumpers JP2 and JP3 for selecting
8-hour or 16-hour delay for AC loss
reporting. Default is immediate. See
Page 18 in "Configuring the APS-6R".
For 240 VAC operation,
PN 50702:B2 4/14/03