7
DETECTION AREA
1)
Detection area spreads out in
front of the sensor at approx.
120° conically.
2)
The size of the detection area
is in proportion to the size of
the ame.
The size of the detection area
increases with an increase in
ame size and duration.
When the object of detection is from a source such as a lighter,
con rm detection throughout the area.
3)
Use the optional BCW-401 universal bracket when area adjustment
is required.
Factory default setting
●
Detection timer : 1 sec.
Detection area
Detection sensitivity : H (100%)
Detection object : Gas flame of lighter [2.75" (7cm)]
Front view : Ceiling mount
Top view : Wall mount
20'
10'
(6m)
(3m)
10' (3m)
20' (6m)
30' (9m)
33' (10m)
9
TROUBLESHOOTING
Trouble
Completely inactive
Sometimes inactive
Activated without
flame
The alarm LED
flashes and buzzer
sounds (5sec./once)
The alarm LED
lights on but buzzer
does not sound
The alarm LED and
buzzer works but the
connected devices are
inactive (when wired)
When the sensor is soiled, clean the cover with a soft cloth moistened with a small amount of cleaning solution.
●
Maintenance
Check operation once a week.
●
Do not fail to check oparation whenever a furniture in the place is moved.
When low battery alarm sounds, change battery for new one immediately.
●
If it is left, it could cause inactiveness of the sensor.
Approx. 120°
Side view : Ceiling / wall mount
10'
20'
16'
10'
(3m)
(6m)
(5m)
(3m)
Check
No battery connected
●
Low battery
●
No power supply (Broken wire or improper wire)
●
Low voltage (When power supply wired)
●
Interrupting rays objects in front of detection area
●
(Glass, transparent resin are interrupting rays objects)
Sensor inside is wet by condensation etc.
●
Improper area setting
●
Detection window is soiled with dust
●
Low battery
●
Low voltage
●
Large electrical noise source such as a redio station or
●
high-voltage wire nearby
Unexpected ultraviolet rays nearby (Ref : 2, ATTENTION)
●
Sensor inside is wet by condensation etc.
●
Low battery
●
(Low battery alarm)
Buzzer "OFF"
●
Poor contact output connection or broken wire
●
The connected unit's trouble
●
8
10'
16'
(3m)
(5m)
10' (3m)
20' (6m)
30' (9m)
33' (10m)
Solve possible problems according to the following table .
If normal operations can not be restored by these corrective actios, contact either
the dealer from whom you bought the unit or TAKEX.
OPERATION CHECK
1. Turn power on, and con rm power on notice
sounds.
(In case of battery use, con rm power on
notice when connecting the battery.)
2. Ignite a lighter etc. within detection area for
more than the set time.
3. After the set time, buzzer sounds intermittently
and LED ashes. (Alarm action)
4. 10sec. after the
ame goes off, the above
〔
alarm action ends.
When external output is used by wiring,
a continuous output is issued during the
above 3. and 4. alarm action.
Con rm the operation of the connected
devices.
Do not use a lighter in no fire
zone because it is dangerous.
In such case, operation test
have to be done in other place
with sensor only.
Corrective action
Connect battery
●
Change battery
●
Correct power supply or replace broken
●
wire
Remove the interrupting rays object
●
Dry out sensor inside, and remove the
●
cause of the wet
Relocate the sensor to appropriate position
●
Use a BCW-401 (optional) and adjust the
●
angle setting
Remove tha dust and soil
●
Change battery
●
Correct power supply
●
Relocate the sensor
●
Remove the origin of the ultraviolet rays,
●
interrupt ultraviolet rays, or relocate the sensor
Dry out sensor inside, and remove the cause of wet
●
Change battery immediately
●
Buzzer "ON"
●
Check the wiring or connection
●
Check the connected unit
●
〔