Canadian Systems - Kidde Gemini II Design, Installation, Operation, And Maintenance Manual

Suppression control panel
Table of Contents

Advertisement

a. Press the down arrow to display the Main Menu.
b. Select 'Set'.
c. Scroll down and select 'Stop Valve Control'.
d. Select 'Add S/valve slave'.
e. The first registered RHU will be shown. Use the
down arrow keys to select the RHU to be set as a
stop valve control slave.
f.
Select OK. A message will be sent to the selected
RHU configuring it as a Stop Valve Control Slave.
When there are one or more Stop Valve Control
Slaves the MCP will react to any Stop Valve mes-
sage as a Stop Valve Control Master.
2. Removing a Stop Valve Control Slave Device:
a. Press the down arrow to display the Main Menu.
b. Select 'Set'.
c. Scroll down and select 'Stop Valve Control'.
d. Select the 'Remove S/valve slave'.
e. The first RHU configured as a Stop Valve Control
Slave will be shown. Use the down and up arrow
keys to select the RHU to be removed from Stop
Valve Control.
f.
Select OK. A message will be sent to the selected
RHU configuring it not to be a Stop Valve Control
Slave. When there are no more Stop Valve Control
Slaves the MCP will not react to any Stop Valve
message as a Stop Valve Control Master.
7-5

CANADIAN SYSTEMS

See Appendix F for installation and configuration require-
ments for Canadian systems.
November 2002
7-15
firealarmresources.com
Kidde Gemini II System
06-235975-001