Kidde Gemini II Design, Installation, Operation, And Maintenance Manual page 108

Suppression control panel
Table of Contents

Advertisement

Kidde Gemini II System
SOLENOID PART NO. 890181
NOTE: MAXIMUM CIRCUIT WIRING RESISTANCE IS TO BE 0.6 OHMS.
SOLENOID PART NO. 48650001
NOTE: MAXIMUM CIRCUIT WIRING RESISTANCE IS TO BE 6.0 OHMS.
S
NOTE: MAXIMUM CIRCUIT WIRING RESISTANCE IS TO BE 2.3 OHMS.
06-235975-001
TB6
S
-
STOPV-
2
3
1
+
STOPV+
TB6
-
STOPV-
S
BLK
+
STOPV+
Details of Wiring Kidde Control Heads to Stop Valve Terminals
FM GROUP A SOLENOIDS
TB6
-
STOPV-
BLK
+
STOPV+
FM GROUP E & G SOLENOIDS
S
NOTE: MAXIMUM CIRCUIT WIRING RESISTANCE IS TO BE 2.3 OHMS.
Details of Wiring FM Sprinkler Solenoids to Stop Valve Terminals
Figure E-7 (con't.) Release Circuit and Stop Valve Terminal Detail
firealarmresources.com
SOLENOID PART NO. 899175
S
BLU
WHT
SAFETY FUSE
NOTE: MAXIMUM CIRCUIT WIRING RESISTANCE IS TO BE 0.6 OHMS.
SOLENOID PART NO. 81-100000--001
S
NOTE: MAXIMUM CIRCUIT WIRING RESISTANCE IS TO BE 3.7 OHMS.
FM GROUP B & D SOLENOIDS
S
BLK
NOTE: MAXIMUM CIRCUIT WIRING RESISTANCE IS TO BE 1.5 OHMS.
TB6
-
STOPV-
BLK
+
STOPV+
E-6
TB6
MICROSWITCH
-
BLK
STOPV-
YEL
+
STOPV+
SOLENOID
TB6
-
STOPV-
BLK
+
STOPV+
TB6
STOPV-
-
+
STOPV+
November 2002