Kidde Gemini II Design, Installation, Operation, And Maintenance Manual page 114

Suppression control panel
Table of Contents

Advertisement

Kidde Gemini II System
Inside the front door, each enclosure has a Dead Front
Panel that protects the operator from hazardous voltages
inside the unit.
Each panel has three access levels: a key lock and two
password-controlled levels as follows.
Level 1: Hardware access only requires no passcode but
allows access to the LIST menu items.
Level 2: Software access requires passcode and allows
access to the LIST, ISOLATE and TEST menu
items.
Level 3: High-level software access requires second
passcode and allows access to the LIST, ISO-
LATE, TEST and SET menu items. Also allows
the change of level 2 and 3 access codes.
F-2.2
Remote Hazard Unit
When an RHU is communicating normally with the MCP,
the RHU Silence and Reset buttons do not function and
the RHU must be silenced and reset from the MCP. In the
event that the RHU loses communication with the MCP, it
may be silenced and reset with its own buttons.
ID
ALM - DETECTOR ZONE 1
ALM - DETECTOR ZONE 2
ALM - MANUAL RELEASE
ALM - WATERFLOW CKT
SUPERVISORY CKT ACTIVATED
TBL - DETECTOR ZONE 1
TBL - DETECTOR ZONE 2
TBL - MANUAL RELEASE
TBL - WATERFLOW CKT
TBL - ABORT CKT
TBL - SUPERVISORY CKT
TBL - GROUND
TBL - COMMS FAULT
TBL - PANEL AC POWER
ABORT CIRCUIT ON
SIGNAL SILENCED
JP1
DISPLAY MODULE 2
DISPLAY MODULE 3
(OPTIONAL)
NOMEX INSULATOR NOT SHOWN FOR CLARITY
06-235975-001
JP1
JP1
(OPTIONAL)
DISPLAY MODULE 1
Figure F-2. LED Display Modules
firealarmresources.com
F-3
INSTALLATION AND CONFIGURATION
Carefully remove the MCP from the packaging and inspect
for damage. The enclosure, Power Supply and MCP mod-
ule should first be installed as outlined in Chapter 7 and the
enclosed Installation Instructions. The following steps de-
scribe the installation of the Display Module(s) (see Figure
F-2).
The following installation of the display
module(s) should be performed prior to the
application of electrical power to the panel.
Connecting or disconnecting the display
module(s) with power to the panel may result
in damage to the MCP module and/or the
display module(s). A ground strap should be
worn.
1. Remove the lower right 3 nuts on the display window
assembly, allowing the Nomex insulator to fold up.
CAUTION - HIGH VOLTAGE
POWER ON ALARM
J5
B:=0.1 0.01 0.1 0.025 0.025 0.003 0.01
C:=5.8428668976 10002 20 0 0 0 8 0 1 1
D:=324000000 324000000 324000000 324000000 324000000 324000000 162000000
Top:=1 1 9 9 9 9 9 9 14 11 0 0 304800 38100 3.7999999523 1 1 1 0 26 23 21 27 0 0 1 11 0 0 6
B:=0.1 0.01 0.1 0.025 0.025 0.003 0.01
D:=324000000 324000000 324000000 324000000 324000000 324000000 162000000
F:=0.025 0.025 0.25 1 2 0 1 1 0 0 1 1 1 1
Top:=1 1 9 9 9 9 9 9 14 11 0 0 304800 38100 3.7999999523 1 1 1 0 26 23 21 27 0 0 1 11 0 0 6
Bottom:=2 1 12 12 12 12 12 12 13 0 3 1 304800 38100 3.7999999523 1 1 1 0 29 22 28 30 0 0 1 7 0 0 2
Silkscreen Top:=26 3 0 0 0 0 11 11 0 0 0 2 0 0 0 0 1 1 0 -1 -1 -1 -1 0 0 0 0 0 0 0
Silkscreen Bottom:=29 3 0 0 0 0 3 3 0 0 3 2 0 0 0 0 1 1 0 -1 -1 -1 -1 0 0 0 0 0 0 0
Silkscreen Bottom:=29 3 0 0 0 0 3 3 0 0 3 2 0 0 0 0 1 1 0 -1 -1 -1 -1 0 0 0 0 0 0 0
A:=235968x4.pcb <> 0 0 0 0 1 1 1 1 1 1 1 1
A:=235968x4.pcb <> 0 0 0 0 1 1 1 1 1 1 1 1
__It__Is__Job__Name__:=235968x4.pcb
P:= 1 1 1 1
P:= 1 1 1 1
E:=0.5 0 0 0.1 0 1
F:=0.025 0.025 0.25 1 2 0 1 1 0 0 1 1 1 1
C:=5.8428668976 10002 20 0 0 0 8 0 1 1
E:=0.5 0 0 0.1 0 1
Bottom:=2 1 12 12 12 12 12 12 13 0 3 1 304800 38100 3.7999999523 1 1 1 0 29 22 28 30 0 0 1 7 0 0 2
__It__Is__Job__Name__:=235968x4.pcb
Silkscreen Top:=26 3 0 0 0 0 11 11 0 0 0 2 0 0 0 0 1 1 0 -1 -1 -1 -1 0 0 0 0 0 0 0
DEADFRONT NOT SHOWN FOR CLARITY
F-2
!
CAUTION
SYSTEM
CONTROLS
SIGNAL
RESET
ALARM
SUP/TBL
SILENCE
SCROLL
SCROLL
CANCEL
MAIN
CONTROL
R
PANEL
ACCEPT
MENU
SIGNAL
CONTROLS
SUPERVISORY
TROUBLE
SILENCED
November 2002