Wiring Diagrams; Recommended Conductor Sizes; Recommended Color Code For Fire Suppression Installations - Kidde Gemini II Design, Installation, Operation, And Maintenance Manual

Suppression control panel
Table of Contents

Advertisement

L
NON-RESETTABLE
POWER
RESETTABLE
L
POWER
S
BATTERIES
120/240 VAC
S
50/60 Hz
MAINS SUPPLY
ALARM CONTACTS
TROUBLE CONTACTS
PROGRAM
CONTACTS
OPTIONAL RELAY BOARD WITH 5 FORM C
PROGRAMMABLE RELAYS
TO NEXT DEVICE
CH 1
L
S
TO NEXT DEVICE
CH 2
L
S
ABORT/SUPV 2
L
S
MANUAL
L
S
RELEASE
SUP 1.
L
S

RECOMMENDED CONDUCTOR SIZES

SIZES
SERVICE
MINIMUM
MAXIMUM
120/240 VAC
#14 AWG
#12 AWG
SUPPLY
INITIATING CIRCUITS
#18 AWG
#12 AWG
ALARM SIGNALLING
#16 AWG
#12 AWG
AUXILIARY CIRCUITS:
120VAC
#14 AWG
#12 AWG
24VDC
#18 AWG
#12 AWG
November 2002
APPENDIX E

WIRING DIAGRAMS

(SEE NOTE 4)
BK
RD
STOP VALVE
S
L
(+)
(-)
(+)
(-)
+
24 VDC
_
+ _
+
- +
RESET
NON-RESET
BATT
AUX 24 V OUT
TB1
TB1000
TB3
TB4
R
R
SUPERVISORY
POWER ON
ALARM
TROUBLE
J1
J1001
TB7
J1000
+
- +
A1 B1 A2 B2
A1 B1 A2 B2
10K
5%
(CLASS B
0.5W
STYLE B)
EOL
10K
(CLASS B
5%
STYLE B)
0.5W
EOL
10K
5%
(CLASS B
0.5W
STYLE B)
EOL
RECOMMENDED COLOR CODE FOR
FIRE SUPPRESSION INSTALLATIONS
MAXIMUM
ALLOWABLE
SINGLE-CONDUCTOR WIRES
WIRING COLOR CODE
WIRE LINE
BLACK = BK
AC POWER HOT
RESISTANCE
AC NEUTRAL
WHITE = WH
---
GREEN = GR
GROUND
50 OHMS (per loop)
R=1/(I ) T
---
---
Figure E-1. MCP Wiring Diagram
firealarmresources.com
S
S
(SEE NOTE 2)
BK
RD
BK
RD
RELEASE OF TWO SOLENOIDS
(-)
(+)
(-)
(+)
-
+
R2- R2+ R1- R1+ 1-
2-
2+
1+
1-
2-
2+
1+
SOUNDER 2
SOUNDER 1
STOP V
RELEASE
TB6
W109
SYSTEM
W108
CONTROLS
SIGNAL
ALARM
SUP/TBL
RESET
SILENCE
SCROLL
SCROLL
MAIN
CANCEL
CONTROL
PANEL
ACCEPT
MENU
SIGNAL
CONTROLS
SILENCED
W101
W104
TB5
- +
- 1+ 2+ 2- 1- 1+ 2+
2-
1- 1+ 2+ 2- 1-
WF
(-)
(-)
(-)
6
7
7
SD
SD
3
3
(+)
(+)
1
2
1
(+)
(-)
(-)
(-)
6
7
7
SD
SD
3
3
(+)
(+)
1
2
1
(+)
NOTES:
1. ALTHOUGH DET1, DET2, AND W-FLOW CIRCUITS ARE
SHOWN AS CLASS A STYLE D AND SOUNDER 1 AND
SOUNDER 2 CIRCUITS ARE SHOWN AS CLASS A STYLE Z,
THESE CAN BE WIRED AS CLASS B STYLE B AND CLASS B
STYLE Y RESPECTIVELY. SEE FIGURE E-2 FOR DETAILS.
2. THE VALUE OF THE RELEASE CIRCUIT DUMMY RESISTOR
IS 2K, 5%, 1 WATT.
3. FOR LIST OF COMPATIBLE DEVICE, REFER TO APPENDIX B..
4. STOP VALVES ARE REQUIRED FOR SYSTEMS
WITH CLUSTERED CYLINDERS. IF UNUSED, TERMINATE
WITH 2k, 5% 1 WATT RESISTOR.
5.
— FOR SUPERVISED CIRCUITS
S
— FOR POWER LIMITED CIRCUITS ROUTED
L
SEPARATELY FROM NON-POWER LIMITED
WIRES BY MORE THAN ¼ INCH. REFER TO
FIGURE E-10.
6.FOR CONFIGURATION OF SHORTING LINKS, REFER TO
FIGURE E-6.
7. FOR DETAILS OF RELEASE CIRCUITS, REFER TO
FIGURE E-7.
8. FOR DETAILS OF RS-485 WIRING, REFER TO FIGURE E-9.
9. FOR CANADIAN APPLICATIONS, ALL FIELD LOCATED EOL
RESISTORS MUST BE MOUNTED IN AN EOL BACKBOX
(P/N 06-129963-001).
E-1
Kidde Gemini II System
SIG. CKT. 2
(CLASS A, STYLE Z)
(SEE NOTE 1)
L
S
SIG. CKT. 1
(CLASS A, STYLE Z)
(SEE NOTE 1)
CHASSIS
AC 120/240
GND.
NEUTRAL
LINE
N
L
WARNING
HIGH VOLTAGES MAY BE PRESENT WHEN
CONNECTING AC POWER TO THE CONTROL PANEL.
TAKE SUITABLE PRECAUTIONS TO AVOID INJURY.
USE 15A BREAKER OR LESSS
WATER-FLOW CKT.
L
S
(CLASS A, STYLE D)
(SEE NOTE 1)
DET. CKT. 2
(-)
6
(CLASS A, STYLE D)
L
S
MAX. 40 DETECTORS
2
(+)
(SEE NOTE 1)
DET. CKT. 1
(-)
(CLASS A, STYLE D)
6
L
S
MAX. 40 DETECTORS
2
(+)
(SEE NOTE 1)
06-235975-001