Printed Circuit Boards; Unit Installation Procedures; Enclosure Mounting Procedure - Kidde Gemini II Design, Installation, Operation, And Maintenance Manual

Suppression control panel
Table of Contents

Advertisement

enclosure must not be exposed to ambient temperatures
below 32°F (0°C) or above 120°F (49°C). Relative humid-
ity should not exceed 93% non-condensing @ 100°F
(36.5°C).
Position the enclosure in a readily accessible and easily
visible location about 44 inches (112 cm) from the floor in
order to place the display panel at a convenient viewing
height. Ensure there is a 1-1/2 foot clearance in front of the
enclosure for the door to swing open.
The Main Control Panel and Remote Hazard Unit enclo-
sures are designed to be surface or semi-flush mounted.
Use screws or bolts no smaller than No. 10 (3/16") in diam-
eter to secure the enclosure to wall studs or masonry walls.
Never mount the enclosure to drywall or plaster walls with-
out securing to studs.
The Remote Display Unit has mounting screw holes on the
sides as well, and can be flush mounted between studs.
The type of hardware is at the discretion of the installer, but
must be in accordance with good electrical and safety prac-
tices. All installation wiring must adhere to NFPA 70 (NEC)
and all state and local codes.
7-3.1.6

PRINTED CIRCUIT BOARDS

Figures 7-2, 7-3 and 7-4 show the layouts of the printed
circuit boards of the MCP, the RHU and the RDU respec-
tively.
TB1: AC Power
AC MAINS INPUT
N
TB4
NO
A
L
C
M
NC
NO
T
B
C
L
NC
P
NO
R
C
O
G
NC
J1
J4
INTERNAL
SOUNDER
TB7: RS-485 data channel
November 2002
TB3: 24 Vdc
output
Battery connection
_
- +
AC & 24V
RESET
PSU PLUG
L
BATT
AUX 24 V OUT
TB1000
W200
2
1
3
W1000
J5
SUPERVISORY
POWER ON
ALARM
J1001
TB7
J1000
A1 B1 A2 B2
A1 B1 A2 B2
Figure 7-2. Main Control Panel Printed Circuit Board
firealarmresources.com
7-3.2

Unit Installation Procedures

The first step in the installation procedure is to prepare sys-
tem layout and wiring drawings. The wiring drawings spe-
cific to a unit should be secured to the inside of its cabinet
after the installation is complete for future reference.
7-3.2.1

ENCLOSURE MOUNTING PROCEDURE

Once the locations of the system units i.e., the MCP, the
RHUs and RDUs is decided, the next step is to mount the
enclosures/backboxes using the following steps:
1. For the MCP and RHU, remove the Power Supply and
PCB/Display Assembly cartons from within the enclo-
sure and place them in a safe location.
2. Mount the MCP and RHU enclosures as follows:
a. Remove the front door of the enclosure. To remove
the front door, remove the ground wire, open the
door about 90° from the closed position and lift it
up until the door hinge pins clear the mating hinge
sockets on the left side of the enclosure.
b. Remove knockouts as required (taking the battery
location at the bottom of the enclosure into consid-
eration).
c. To mount against a wall, place the mounting screws
(not provided) in the wall to match the keyholes at
the back of the enclosure. Leave about ¼" of both
TB6: Indicator, release and
stop valve outputs
+ _
+
-
+
R2- R2+ R1- R1+ 1-
2-
2+
1+
1-
NON-RESET
STOP V
RELEASE
SOUNDER 2
SOUNDER 1
TB3
TB6
SYSTEM
CONTROLS
SIGNAL
ALARM
RESET
SILENCE
SCROLL
MAIN
CONTROL
R
R
PANEL
MENU
CONTROLS
SIGNAL
TROUBLE
SILENCED
LCD
W101
CONTRAST
VR1
TB5
- +
+
- +
- 1+ 2+ 2- 1- 1+ 2+
2-
Shorting link W104; pins 1-4 are for
waterflow input and pins 5-8 are for
Shorting link W101,
the data highway
detection input circuit
7-3
Kidde Gemini II System
2-
2+
1+
W109
Shorting links W 108 & W109,
sounder output circuit
SUP/TBL
W108
SCROLL
CANCEL
ACCEPT
W104
1- 1+ 2+ 2- 1-
06-235975-001

Advertisement

Table of Contents
loading

Table of Contents