Kidde Gemini II Design, Installation, Operation, And Maintenance Manual page 104

Suppression control panel
Table of Contents

Advertisement

Kidde Gemini II System
NON-RESETTABLE
L
POWER
RESETTABLE
L
POWER
24 VDC
S
BATTERIES
120/240 VAC
50/60 Hz
S
MAINS SUPPLY
OPTIONAL RELAY BOARD WITH 5 FORM C
PROGRAMMABLE RELAYS
FROM PREVIOUS DEVICE
CH 1
L
S
TO NEXT DEVICE
CH 1
FROM PREVIOUS DEVICE
CH 2
L
S
TO NEXT DEVICE
CH 2
L
ABORT/SUPV 2
S
MANUAL
S
L
RELEASE
SUPV 1
S
L
SWITCH SW2 SETTINGS FOR REMOTE HAZARD
UNIT NETWORK ADDRESS
RHU
Network Address
SW2-1
1
OFF
2
ON
3
OFF
4
ON
5
OFF
6
ON
7
OFF
INVALID
ON
06-235975-001
(SEE NOTE 4)
BK
RD
S
BK
STOP VALVE
L
S
(+)
(-)
(+)
(-)
+
-
+ _
-
+
-
-
+
RESET
NON-RESET
TB1
TB1000
TB3
POWER ON
ALARM
SUPERVISORY
TROUBLE
J1
J1001
TB7
J1000
+ - + -
+ -
A1
B1
A2
B2
A1 B1 A2 B2
10K
5%
(CLASS B
0.5W
STYLE B)
EOL
10K
(CLASS B
5%
0.5W
STYLE B)
EOL
10K
5%
(CLASS B
0.5W
STYLE B)
EOL
Switch Position
SW2-2
SW2-3
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
OFF
ON
OFF
ON
ON
ON
ON
ON
Figure E-2. RHU Wiring Diagram
firealarmresources.com
RELEASE OF TWO SOLENOIDS
(SEE NOTE 2)
S
RD
BK
RD
(-)
(+)
(-)
(+)
+
R2-
R2+
R1-
R1+
1-
2-
2+
1+
1-
2-
2+
1+
TB6
W109
W108
SIGNAL
SILENCE
RESET
SYSTEM
CONTROLS
REMOTE
HAZARD
ALARM
SCROLL
R
R
UNIT
SUP/TBL
SCROLL
SIGNAL
SILENCED
SW2
W101
W104
TB5
1+
2+
2-
1-
1+
2+
2-
1-
1+
2+
2-
1-
WF
(-)
(-)
(-)
6
7
7
SD
SD
3
3
(+)
(+)
1
1
2
(+)
(-)
(-)
(-)
7
6
7
SD
SD
3
3
(+)
1
2
(+)
1
(+)
NOTES:
1. ALTHOUGH DET1, DET2, AND W-FLOW CIRCUITS ARE
SHOWN AS CLASS B STYLE B AND SOUNDER1 AND
SOUNDER2 CIRCUITS ARE SHOWN AS CLASS B STYLE Y,
THESE CAN ALSO BE WIRED AS CLASS A STYLE D AND
CLASS A STYLE Z RESPECTIVELY. SEE FIGURE E-1
FOR DETAILS.
2. THE VALUE OF THE RELEASE CIRCUIT
DUMMY RESISTOR IS 2K, 5%, 1 WATT.
3. FOR LIST OF COMPATIBLE DEVICES, REFER TO APPENDIX B.
4. STOP VALVES ARE REQUIRED FOR SYSTEMS WITH CLUSTERED
CYLINDERS. IF UNUSED, TERMINATE WITH 2K, 5% 1WATT RESISTOR.
S
5.
- FOR SUPERVISED CIRCUITS
- FOR POWER LIMITED CIRCUITS ROUTED
L
SEPARATELY FROM NON-POWER LIMITED
WIRES BY MORE THAN ¼ INCH. REFER TO FIGURE E-10.
6.FOR CONFIGURATION OF SHORTING LINKS, REFER TO
FIGURE E-6.
7.FOR DETAILS OF RELEASE CIRCUITS, REFER TO
FIGURE E-7.
8.FOR DETAILS OF RS-485 WIRING, REFER TO FIGURE E-9.
9. FOR CANADIAN APPLICATIONS, ALL FIELD LOCATED EOL
RESISTORS MUST BE MOUNTED IN AN EOL BACKBOX
(P/N 06-129963-001).
E-2
10K
SIG. CKT. 2
5%
L
(CLASS B, STYLE Y)
S
0.5W
(SEE NOTE 1)
EOL
10K
SIG. CKT. 1
5%
S
(CLASS B, STYLE Y)
L
0.5W
(SEE NOTE 1)
EOL
AC 120/240
CHASSIS
GND.
NEUTRAL
LINE
N
L
WARNING
HIGH VOLTAGES MAY BE PRESENT WHEN
CONNECTING AC POWER TO THE CONTROL PANEL.
TAKE SUITABLE PRECAUTIONS TO AVOID INJURY.
USE 15A BREAKER OR LESS
10K
WATER-FLOW CKT.
5%
S
(CLASS B, STYLE B)
0.5W
(SEE NOTE 1)
EOL
3.9K
DET. CKT. 2
(-)
6
5%
(CLASS B, STYLE B)
S
0.5W
MAX. 40 DETECTORS
2
(+)
EOL
(SEE NOTE 1)
3.9K
DET. CKT. 1
(-)
5%
(CLASS B, STYLE B)
6
S
0.5W
MAX. 40 DETECTORS
2
(+)
EOL
(SEE NOTE 1)
L
L
L
November 2002