8 on W104 on the MCP printed circuit board (see Ap-
pendix E). If the last unit on the network is an RHU,
short the same pins on W104 on that RHU. However, if
the last unit is an RDU, short pins 1 to 2 and 3 to 4 on
W1 of that RDU (see Appendix E). Refer to Figures 7-
2 and 7-3 for the location of shorting links W104 on the
MCP and RHU respectively and Figure 7-4 for the lo-
cation of shorting link W1 on the RDU.
2. Connect Channel 1 on TB7 on the MCP to Channel 1
on TB7 of the first unit (either RHU or RDU) on the
network. If the communications line is working prop-
erly the status display indicates that communications
has been established but the unit is still not registered.
3. Disconnect Channel 1 and connect Channel 2. Ensure
that Channel 2 is working properly.
4. Connect both channels.
5. Register the unit and enter configuration parameters
as described in Paragraph 7-4.
6. Connect another unit and follow the same procedure.
Register it in the MCP and enter configuration param-
eters.
7. Test the system for proper functionality.
7-4

CONFIGURATION PROCEDURES

Configuration parameters as shown in Figure 7-10 for all
the system units are entered at the MCP, which then trans-
mits this data to the appropriate RHUs and RDUs via the
RS-485 communications link.
An error message is generated if the MCP is unable to do
so. Perform the steps detailed in the following paragraphs
to enter the configuration parameters for the System.
7-4.1
Setting the Password
The Set, Isolate and Test menus are password protected.
The factory default password is 1234. To set a new four-
digit password, perform the following steps:
1. Press the down arrow to display the Main Menu.
2. Select Set.
3. Select Password. The following figure displays:
Set Password
****
x
Figure 7-8. Setting the Password
4. Ensure that the cursor (x) is below the first asterisk. To
create a new password, press the up arrow to select a
digit. Once selected, use the right arrow to move to the
second asterisk. Select a digit and move to the next
asterisk and so on.
5. Press the right arrow to move the cursor to OK and
press ACCEPT to return to the main menu.
November 2002
O K
Cancel
firealarmresources.com
7-4.2
Setting the Date and Time
1. To set the Time for the entire system (to ensure that all
clocks in the system are synchronized), perform the
following steps:
a. Press the down arrow to display the Main Menu.
b. Select Set.
c. Select Set Time. Time is displayed in 24-hour for-
mat: HH/MM. The cursor appears as an X in the
bottom line (see Figure 7-9).
Set time
12:13 OK Cancel
X
Figure 7-9. Time Menu
d. To set the Hour, ensure the X is below the Hour
and use the up and down arrow keys to display
correct hour.
e. To set the Minutes, press the right arrow to move
the X below the Minutes. Use the up and down ar-
row keys to display the correct minutes.
f.
Press the right arrow to move the X under OK and
press ACCEPT.
g. Check the time display. If correct, press ACCEPT
to return to the Main Menu.
2. To set the Date for the entire system (to ensure that all
clocks in the system are synchronized), perform the
following steps:
a. Select Set Date from the Main Menu. The date is
displayed in the MM/DD/YY format. There is no
automatic adjustment for daylight savings time.
b. To make a setting, place the X under the month,
day or year. Use the up and down arrow keys to
increase or decrease the field.
c. To save the date, move the X under OK and press
ACCEPT. A confirmation message displays.
7-4.3
Configuring the MCP and RHUs
To access the configuration parameters for the MCP and
each RHU, perform the following:
1. First press the down arrow to display the Main Menu.
2. Select Set
3. Select Configuration
4. Then select either the MCP or an RHU to be config-
ured. Press ACCEPT and then the down arrow key for
the following conditions:
a. Global or Local mode: In Global mode, the display,
buzzer, silence button and silence light at the RHU
mimic those on the MCP i.e., annunciating system-
7-11