Do not plug the ribbon cable into the left-hand
connector of Display Module 1 as damage to
the MCP and/or the Display Module may result.
2. Plug the long ribbon cable supplied with the panel into
the right hand connector (when viewed from inside the
panel door) of Display Module 1. Plug the other end of
the ribbon cable into J5 of the MCP module.
Note: The ribbon cable is reversible.
3. If additional Display Modules (P/N 84-322001-013) are
required, these should be installed at this time. Remove
the nut on the uppermost edge of the window assem-
bly, to the left of Display Module 1. Install two nylon
spacers and Display Module 2 onto the top and bottom
threaded studs, with the LEDs facing the window as-
sembly. Secure in place with the top nut. Plug the sup-
plied 2-inch ribbon cable between Display Modules 1
and 2.
Note: The ribbon cable is reversible.
4. Repeat step 3 if Display Module 3 is required, installing
into the third display position, and plugging into Display
Module 2.
5. Prior to the application of power, the Display Modules
must be configured for correct supervision as follows:
Component JP1, which is located on the visible side of
each Display Module (and shown in Figure F-2) must
be cut on every Display Module except the last one on
the "daisy chain". That is, if only Display Module 1 is
installed, no action is required. If 1 and 2 are installed,
JP1 must be cut on 1 and left intact on 2. If 1, 2 and 3
are installed, JP1 must be cut on 1 and 2 and left intact
on 3.
6. Fold down and locate the Nomex insulator over the 3
lower right studs and secure in place with the 3 nuts.
7. Remove the adjacent slide-in label(s) corresponding
to the installed Display Modules, and write a short de-
scription of the protected zone. Also, for the LED la-
beled as "Abort/Supv #2 Ckt," use a black ink
permanent marker to black out the type of circuit which
is unused. Thus, if the circuit is configured as "Supv
#2," black out "Abort" and vice-versa. Replace the la-
bel, white printed side facing the panel front. Labels for
unused Display Modules may be reversed.
8. Install the dead front panel, by locating on the lower lip
of the enclosure, and attach using the supplied screws
at the top. Care must be taken not to pinch the display
ribbon cable.
9. Power may now be applied to the panel, and the sys-
tem configured as described in Chapter 7.
November 2002
10. Correct installation of the Display Modules may be
F-4
During walk test, the display board LEDs remain off. Dur-
ing LED test (invoked by simultaneously pressing the SUPV/
TBL Scroll and Alarm Scroll buttons on the MCP mem-
brane), the LEDs flash, one second on, followed by two
seconds off. The membrane display will show a System
Trouble in the event that any Display Modules or intercon-
necting cables are missing.
F-5
Refer to Appendix A for battery calculations for cUL sys-
tems.
F-6
Devices used in Canadian applications shall be as listed in
Appendix B, Paragraph B-2 and/or shall be cUL/ULC listed
devices compatible with circuit specifications listed in Table
1-3, 1-4 and 1-5 of this manual.
F-3
firealarmresources.com
Kidde Gemini II System
checked by invoking the LED/Display test. Press the
SUPV/TBL Scroll and Alarm Scroll buttons simulta-
neously. All LEDs should light momentarily.